Swimming pool heat pump
- 47 -
R05——Stop differential of cooling
This represents the difference between R01 and stop cooling point.
R06——Start differential of heating
This represents the difference between R02 and start heating point.
R07——Stop differential of heating
This represents the difference between R02 and stop heating point.
R08——Min. set point in Cooling
Establishes the minimum limit for setting the Cooling set point
R09——Max. Cooling set point
Establishes the maximum limit for setting the Cooling set point
R10——Min. Heating set point
Establishes the minimum limit for setting the Heating set point
R11——Max. Heating set point
Establishes the maximum limit for setting the Heating set point
Compressor action at cooling mode
R02+R07
R02-R06
R02
R02
Compressor on
Compressor off
Water inlet temperature
Compressor action at heating mode
Compressor action at Automatic mode
R01
R01+R04
R01
R01-R05
Compressor on
Compressor off
Water inlet temperature
R03-R06
R03+R04
R03
Compressor on
Compressor off
Water inlet temperature
Cooling
Heating