Menu 12: 47 Vdc or higher
• Voltage set-point to switch from Grid mode to Off-Grid mode when selecting “SBU priority” or “Solar / PV
first” in settings menu 01
Menu 13: 52 Vdc or lower
• Boost battery charging voltage
Menu 26: 52.7 Vdc
• Floating battery charging voltage
Menu 27: 51.5 Vdc
• Low voltage disconnect
Menu 29: 46.0 Vdc
• Boost battery charging duration
Menu 32: 120 min
• Battery equalization
Menu 33: Disabled
• Maximum discharging current
Menu 41: Disabled
8. Once the settings have been applied, exit the settings menu by pressing to return to the main view.
9. Activate the circuit breakers or insert the fuses to energize the various inputs and outputs on the Any-Grid in
the following order (skip any that are not connected):
a) AC input
b) PV input
c) AC output
10. If you are using more than one Any-Grid, this procedure ensures that the unit to which the Leoch battery is
connected, will communicate with the Leoch battery BMS. Automatically, the battery type of all other
connected Any-Grid units will be set to “User-defined”, this is normal.
The commissioning and programming of the battery-related settings of the Any-Grid is now complete.