Phocos Any-Grid series
Pure Sine Wave Hybrid Inverter Ch arger with
MPPT Solar Charge Controller
PSW-H-8kW-230/48V
PSW-H-5kW-230/48V
PSW-H-3kW-230/24V
PSW-H-6.5kW-120/48V
PSW-H-5kW-120/48V
PSW-H-3kW-120/24V
User and Installation Manual
English
For further languages see
Für weitere Sprachen siehe
Pour autres langues voir
Para otros id iomas ver
对于其他语言请参阅
www.phocos.com

Other manuals for Phocos Any-Grid Series

Questions and Answers

  • B
    Brian VazquezSep 4, 2025
    How to fix Phocos Battery Charger when the unit shuts down automatically during start-up process?
    • J
      Jennifer JacksonSep 4, 2025
      If your Phocos Battery Charger shuts down automatically during the start-up process, it's likely because the battery voltage is too low (less than 45.84V/22.92V for the 48V/24V model). To resolve this, first try to re-charge the battery. If the issue persists, you may need to replace the battery.
  • D
    Daniel SosaAug 25, 2025
    Why does my Phocos Inverter show error A011?
    • E
      Eugene NovakAug 25, 2025
      If the Phocos Inverter displays error A011, it indicates that the public grid disconnected. Check if the inverter AC connection is correct.
  • W
    wwestAug 25, 2025
    What does error E005 mean on my Phocos Inverter?
    • D
      Dr. Lee SawyerAug 26, 2025
      If the Phocos Inverter displays error E005, this indicates an internal AC overcurrent.
  • M
    Mr. Christopher Jackson MDSep 12, 2025
    Why Phocos Controller battery voltage is too high?
    • B
      Beverly MendozaSep 12, 2025
      If the battery voltage is too high on your Phocos Controller, check if the specifications and quantity of batteries meet the requirements.
  • P
    Philip OwensSep 18, 2025
    What to do if my Phocos Battery Charger shows that the battery is over-charged?
    • M
      Michael HoldenSep 18, 2025
      If your Phocos Battery Charger indicates that the battery is over-charged, return it to a repair center.
  • B
    Bradley DiazSep 8, 2025
    What to do if EEPROM corrupted on Phocos Any-Grid Battery Charger?
    • C
      cameronsmithSep 8, 2025
      Please contact your repair center and communicate the serial number of the affected unit.
  • E
    Eric VillegasAug 31, 2025
    What does error E013 mean on a Phocos Inverter?
    • K
      Kevin WebbAug 31, 2025
      If the Phocos Inverter shows error E013, it indicates an internal memory error.
  • T
    tbeltranSep 23, 2025
    What to do if my Phocos Any-Grid Battery Charger displays fault code 83?
    • A
      Allen GoodmanSep 23, 2025
      If your Phocos Battery Charger displays fault code 83, which means that the detected battery voltage differs between units, make sure all inverters share the same battery bank.
  • G
    George JohnsonSep 15, 2025
    What to do if my Phocos Any-Grid shows fault code 85 - AC output current unbalanced?
    • L
      Laurie AllenSep 15, 2025
      If your Phocos Battery Charger displays fault code 85 indicating AC output current is unbalanced, try restarting the inverter. If the issue persists, remove excessive loads and re-check the load information from the LCD of the units.
  • A
    Amber JonesAug 28, 2025
    What does error E009 mean on a Phocos Inverter?
    • W
      william08Aug 28, 2025
      If the Phocos Inverter shows error E009, it means the master-slave DSP communication is disabled or there is an error of master-slave DSP check bit.

Summary

Introduction

General Safety Warnings and Precautions

Crucial safety warnings and precautions for installation and maintenance.

Installation

Battery Connection Procedures

Detailed steps and warnings for safely connecting the battery to the unit.

AC Input and AC Output Connection

Instructions for connecting the AC power source and loads to the inverter.

PV Connection Procedures

Guidance on connecting the solar PV array to the inverter, including voltage/current limits.

Multi-Unit Installation (Parallel, Split-Phase, 3-Phase)

Instructions for connecting multiple Any-Grid units in various system configurations.

Operation

Device Operation Settings Configuration

Guide to navigating and setting various operational parameters of the inverter.

Fault Reference Codes

Fault Code Interpretation

Lists fault codes, their events, and corresponding screen views for troubleshooting.

Warning Codes

Warning Code Interpretation

Lists warning codes, associated events, audible alarms, and screen views.

Troubleshooting

Troubleshooting Common Issues

Addresses problems like unit shutdown, no response, AC source issues, and relay problems.

Specifications

Warranty and Liability

Phocos Any-Grid Series Specifications