www.phocos.com 52 | P a g e
Fault code 84
The detec ted AC input
voltage and frequency
differ between units.
1. Check the AC input wiring
connection and restart the unit.
2. Make s ure the AC source starts
up with the same voltage and
freque ncy on each phase. If there
are breakers installed between
AC inout and Any-Grid units,
please be sure all breakers can be
turne d on the AC input at same
time.
3. If the problem still remains,
please contact your repair center.
Fault code 85
AC output current
unbalanced
1. Restart the inverter.
2. Remove excess ive loads and re-
check load information from LCD
of units. If the value s are different
between units on the same
phase, please check if AC input
and output cables are the same
length, cross-se ction and
material.
3. If the problem remains, please
contact your repair center.
Fault code 86
AC output mode setting
is different between units.
1. Switch off the units and check
settings menu number 2 8.
2. For parallel systems on a single
phase, make sure each unit is set
to “PAL” in settings menu number
28.
For plit-phase and 3-phase
systems, make sure each unit has
the same two first characters in
settings menu number 2 8 (“2P”
for s plit-phase “3P”for 3-phase)
and is on the correct phase.
3. If the problem remains, please
contact your repair center.
Fault code 90 EEPROM corrupted
Please contact your repair center and
communicate the serial number of
the affected unit.
12.0 Specifications
12.1 Grid Mode
Model
PSW-H-8KW-
230/48V
PSW-H-5KW-
230/48V
PSW-H-3KW-
230/24V
PSW-H-5KW-
120/48V
PSW-H-6.5KW-
120/48V
PSW-H-3KW-
120/24V
AC Input Voltage Waveform Pure Sine Wave ( utility or generator)
Nominal AC InputVoltage 230 Vac 120 Vac
Maximum AC Input Current
60 Aac
40 Aac 30 Aac
60 Aac 38.3 Aac