When the battery voltage is indicated as low, it is recommended
to use the remaining energy economically. The charge controller
will subsequently switch off the load.
OK (LED off)
low (LED on)
Battery voltage display
In case of deep discharge or overload/short-circuit, the load output
is switched off. This is indicated by:
Load status display
(LED flashing)
Overload or
Short-circuit of load
(LED off)
Normal
operation
(LED on)
Low voltage
disconnect
The controller is equipped with a low voltage disconnection function
to protect the battery against a deep discharge: This function is
controlled by the voltage, and automatically switches off the load
output at a battery voltage lower than 11.5V. As soon as the battery
reaches a voltage of 12.5V, the load output is switched on again.
Low Voltage Disconnect Function (LVD)
22
very low
(LED flashing)