11
e
n
g
l
i
s
h
5. Connections
1 10-30 VDC
2 GND 1
3 GND 1
4 Latch
5I
6 GND 2
7U
4.11 End of programming
Programming routine will
b
e passed through once
again. All parameters can
be checked.
Programming routine will
be left and the new pa ra -
me ters will be stored. Af ter -
wards the device is ready
to use.
6. Technical data
Anzeige: Display:
5digit 7 segment red
LED-Display,
8 mm high characters
Range of input signals
0 .. 10 V DC
2 .. 10 V DC
0 .. 20 mA DC
4 .. 20 mA DC
Accuracy: < 0.1% ± 1 digit at an ambient tempe-
rature of 20 °C
Zero adjustment:
automatic
Temperature drift:
<70ppm/K
Measuring rate:
0,5 Measurement/sec ...
2 Measurement/sec
Current measuring:
Voltage drop:
max. 2,0 V at 20 mA
Current limitation: 50 mA
Voltage measurement:
I
nput resistance: >1 MW
Elimination of power line hum:
digital filter at 50 Hz
Supply voltage:
10...30 VDC,
g
alvanically isolated
Current consumption:
max. 50 mA
Ambient temperature:
-10°C ... +50°C
Storage temperature:
-25°C ... +70°C
Data retention:
via EEPROM 1 Mio.
memory cycles or 10 years
Weight: ca. 50 g
Protection: IP 65 (front)
EMC:
Noise emission: EN 55 011 Class B
Noise immunity: EN 61 000-6-2
Cleaning:
The front of the unit is only to be cleaned with a soft
wet (water !) cloth.
Error messages:
Err 0* Error/defect in A/D-part
Err 3* Error/defect EEPROM
Err 4** Analogue input overflow
Err 5* Error/defect EEPROM. Device not cali-
brated
* Please send the device back for checking
** Please check input signal and programming
7. Delivery includes:
- Digital display with analogue inputs
- Panel mounting clip
- Bezel for screw mount, panel cut-out
50x25 mm
- Bezel for clip mount, panel cut-out
50x25 mm
- Sealing
- Tack dry symbols