6.6.5 RAD-DI8-IFS process data
I/O module Module type ID Register Address range Function code
RAD-DI8-IFS
02
hex
Static mode
02
hex
Static inputs
30xx0 ... 30xx1
1
1
xx = I/O MAP address set using the white thumbwheel
fc 04
40
hex
Pulse counter
mode
06
hex
Pulse inputs
30xx0 ... 30xx5
1
fc 04
40
hex
Pulse counter
mode
02
hex
Reset counter
states
40xx0 ... 40xx1
1
fc 03, 16
Table 6-13 RAD-DI8-IFS module type and timeliness of data
30xx0
1
1
xx = I/O MAP address set using the white thumbwheel
Module type and timeliness of data
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Y
2
2
Y = timeliness of data, bit 8
If the data in the register is not up to date, then the register value is 1. This is the case, for example, if the
wireless connection or communication with an input module fails. In this case, the IN process data is re-
tained in the Modbus table, but is no longer updated.
Module type
3
3
If the module type in the register is invalid or not available, then the register value is 0.