RAD-...-IFS
108 / 198
PHOENIX CONTACT 105542_en_05
Use DIP switch 1 to select static mode or pulse counter mode.
Disconnect the device from the supply voltage.
Switch the supply voltage back on.
The selected mode is now active.
7.5.4 Functions in pulse counter mode
The counter state can only increase consecutively. When the maximum counter limit of
4294967295 is reached, the counter state is automatically reset to 0.
There are also three ways to reset the counter state manually:
Via power up
Disconnect the device power supply and then reconnect the voltage.
Via Modbus/RTU register
Reset the counter states via Modbus/RTU as follows:
DI1: bit 0 = 1 (register 40xx1)
DI7: bit 1 = 1 (register 40xx1)
By setting the inputs
Set the corresponding input for at least 0.5 seconds:
–Set input DI3 in order to reset counter state DI1.
–Set input DI5 in order to reset counter state DI7.
Table 7-8 DIP switches of the RAD-DI8-IFS
DIP switch
Input Output signal 1 2 3 4
Digital IN
DI1 ... DI8
Static mode OFF n.c. n.c. n.c.
Counter IN
DI1 + DI7
Pulse counter mode ON n.c. n.c. n.c.
n. c. = not connected, DIP switches 2 ... 4 have no function

Table of Contents

Other manuals for Phoenix Contact RAD-RS485-IFS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact RAD-RS485-IFS and is the answer not in the manual?

Phoenix Contact RAD-RS485-IFS Specifications

General IconGeneral
BrandPhoenix Contact
ModelRAD-RS485-IFS
CategoryTransceiver
LanguageEnglish

Related product manuals