EasyManuals Logo

Phoenix Contact RAD-RS485-IFS User Manual

Phoenix Contact RAD-RS485-IFS
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #156 background imageLoading...
Page #156 background image
RAD-...-IFS
156 / 198
PHOENIX CONTACT 105542_en_05
Table 9-2 Detecting and removing errors: I/O extension module
LED,
I/O module
Current state and possible
cause
Solution
PWR off
No power supply, mains proba-
bly switched off
Switch on the mains, restore the power supply.
DAT off
No communication between
wireless module and
I/O extension module. The wire-
less module is probably in “serial
data” mode.
Check whether the I/O extension module is properly snapped onto
the DIN rail connector and whether it is connected to the wireless
module.
Check the operating mode of the wireless module using the
PSI-CONF software. The wireless module must be in “I/O data”,
“PLC / Modbus/RTU” mode or in dual mode (see page 38).
Reset the wireless module to the default settings (I/O data mode,
see page 30), if necessary.
ERR on
Critical internal error
Example: technical defect
Please contact Phoenix Contact technical support.
ERR flash-
ing slowly
(1.4 Hz)
I/O MAP address changed
Example: the white thumbwheel
setting has accidentally been
modified and the modification
has not yet been confirmed via
the SET button.
Check the I/O MAP address setting on the white thumbwheel of the
I/O extension module.
If necessary, set the correct I/O MAP address and press the SET
button on the wireless module.
In I/O data mode
ERR flash-
ing fast
(2.8 Hz)
Missing input module
Example: an output module is
not assigned the corresponding
input module with the same
I/O MAP address.
Check whether an input module with the same I/O MAP address has
been assigned to every output module.
Use the white thumbwheel on the extension module to set the
I/O MAP address (01 ... 99). The input module must be provided with
the same I/O MAP address as the assigned output module at anoth-
er station.
No bus communication,
no wireless connection present
See measures for the wireless module, page 153
In PLC / Modbus/RTU mode
ERR flash-
ing fast
(2.8 Hz)
No Modbus communication
(safe state of outputs, depend-
ing on DIP switch settings)
Check the communication line between the Modbus/RTU controller
and the master wireless module using RAD ID 01.
Check the wiring of the RS-232/RS-485 connections on the master
and the PLC.
Check the serial interface settings (baud rate, parity, data bits, and
stop bits) on the master and the PLC (from page 38 onwards).
Check whether the I/O extension module is properly snapped onto
the DIN rail connector.
Use the PSI-CONF software to check if the wireless module is in
“PLC / Modbus/RTU” mode or in dual mode (see page 38).
Press the SET button on the wireless module or carry out a power up
in order to read the station structure.
No bus communication,
no wireless connection present
See measures for the wireless module, page 153

Table of Contents

Other manuals for Phoenix Contact RAD-RS485-IFS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact RAD-RS485-IFS and is the answer not in the manual?

Phoenix Contact RAD-RS485-IFS Specifications

General IconGeneral
BrandPhoenix Contact
ModelRAD-RS485-IFS
CategoryTransceiver
LanguageEnglish

Related product manuals