6.6.1 RAD-AI4-IFS process data
I/O module Module type ID Register Address range Function code
RAD-AI4-IFS 20
hex
06
hex
30xx0 ... 30xx5
1
1
xx = I/O MAP address set using the white thumbwheel
fc 04
Table 6-9 RAD-AI4-IFS module type and timeliness of data
30xx0
1
1
xx = I/O MAP address set using the white thumbwheel
Module type and timeliness of data
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Y
2
2
Y = timeliness of data, bit 8
If the data in the register is not up to date, then the register value is 1. This is the case, for example, if the
wireless connection or communication with an input module fails. In this case, the IN process data is re-
tained in the Modbus table, but is no longer updated.
Module type
3
3
If the module type in the register is invalid or not available, then the register value is 0.
30xx1 Reserved
30xx2 Analog input 1 (terminal point 2.x)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
AI1
30xx3 Analog input 2 (terminal point 3.x)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
AI2
30xx4 Analog input 3 (terminal point 4.x)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
AI3
30xx5 Analog input 4 (terminal point 5.x)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
AI4
30xx6 ... 30xx9 Reserved

Table of Contents

Other manuals for Phoenix Contact RAD-RS485-IFS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact RAD-RS485-IFS and is the answer not in the manual?

Phoenix Contact RAD-RS485-IFS Specifications

General IconGeneral
BrandPhoenix Contact
ModelRAD-RS485-IFS
CategoryTransceiver
LanguageEnglish

Related product manuals