10 OF 12 PCS300 SERIES INSTALLATION GUIDE 650-321-017 08/16 ©2014 Phoenix Controls Specifications subject to change without notice. Rev. C
2.6 Specifications
PHS300-x PCS300-x PCS300-X-DOS
POWER
10 to 35 Vdc (24 Vdc recommended)
Note: Use of PVC350-HW is required for LON applications
POWER
CONSUMPTION
With humidity output of:
———
4-20 mA
20 mA (0.5 VA)
0 to 5 Vdc or to 10 Vdc
4 mA (0.1 VA)
SENSING ELEMENTS Thermistor
10 KΩ @ 25
º
C, Type 2
Temperature Range
32
º
to 122
º
F (0
º
to 50
º
C)
Temperature Accuracy
±0.36
º
F, ( ± 0 . 2
º
C)
Temperature Stability
<0.036
º
F / Year (<0.02
º
C / Year)
Heat Dissipation
4.9 mW /
º
F (2.7 mW /
º
C)
Humidity
Humidity Range 0-100% RH
Humidity Accuracy
± 2.0% RH (from 10 to 90% RH at 77
º
F (25
º
C)
Response Time 20 seconds for a 63% step
FEATURES Display
LDC; 3.5 digits at 0.6" H
Te m pe r a tu r e
——
32
º
to 122
º
F (0
º
to 50
º
C)
in 0.5
º
increments
Humidity
——
0 to 100% RH in 0.5% increments
Format
——
Default: Temperature and Humidity
toggled every 5 seconds; Temp Setpoint
only when slider moved
Tem p Se tpo in t
——
Slide pot
Cool / Warm (Down / Up)
Configurable at valve UI:
Absolute 32-122
º
F (0-50
º
C)
Relative -18 to +18
º
F (-7 to +7
º
C)
Temp Setpoint Display Range
——
Shown in 1
º
increments:
Feature 2
——
± 2
º
F (± 2
º
C)
Feature 3
——
± 3
º
F (± 3
º
C)
Feature 7
——
55 to 85
º
F (13 to 30
º
C)
Feature 8
——
60 to 80
º
F (15 to 27
º
C)
Feature 9
——
65 to 80
º
F (18 to 27
º
C)
Override
——
N.O. Pushbutton (closed during push)
Override Display
——
Occupancy "person" icon
Solid=Occupied
Tes t an d Bala nc e
3-position slide switch (High / Norm / Low)
Network Connection 1.8" (3.5 mm) phone jack in base
OUTPUTS Temperature
Resistance, NTC
Tem p er a tu re Se t po in t
——
0-20 KΩ
Occupancy
——
N.O. contact
Humidity as Voltage 0-5 or 0-10 Vdc; Impedance > 10 KΩ
Humidity as Current 4-20 mA; Impedance <500 ohm @ 24 Vdc
ENCLOSURE Material Type ABS Plastic
Material Rating UL 94, V-0
MOUNTING Drywall Anchor and screws provided
Junction Box Standard 2" x 4" J-box; screws provided (not box)
ENVIRONMENTAL Temperature
32
º
to 122
º
F (0
º
to 50
º
C)
Humidity 0 to 95%, non-condensing