EasyManua.ls Logo

Pilz PNOZ m ES EtherNet/IP - Operation; Messages and LED Status

Pilz PNOZ m ES EtherNet/IP
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
Operating Manual PNOZ m ES EtherNet/IP
1003387-EN-05
20
7 Operation
When the supply voltage is switched on, the PNOZmulti safety system copies the configur-
ation from the chip card.
The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base
unit.
The fieldbus module PNOZ m ES EtherNet/IP is configured and started automatically. The
LEDs "MS", "NS", "L/A1" and "L/A2" indicate the status of the PNOZ m ES EtherNet/IP on
the EtherNet/IP.
7.1 Messages
Legend
LED on
LED flashes
LED off
LED Meaning
Power green Supply voltage is present
Supply voltage is not present
L/A1 green Bus connection present at X1 (100 Mbit/s)
green Data traffic present at X1 (100 Mbit/s)
orange Bus connection present at X1 (10 Mbit/s)
orange Data traffic present at X1 (10 Mbit/s)
Bus connection is not available at X1
L/A2 green Bus connection present at X2 (100 Mbit/s)
green Data traffic present at X2 (100 Mbit/s)
orange Bus connection present at X2 (10 Mbit/s)
orange Data traffic present at X2 (10 Mbit/s)
Bus connection not available at X2
MS No supply voltage on PNOZ m ES EtherNet/IP
green The fieldbus module PNOZ m ES EtherNet/IP is operating correctly
green The fieldbus module PNOZ m ES EtherNet/IP is not configured
red Recoverable fault
red Major internal error (not recoverable)
green/red Self test after switching on the supply voltage