9.3.3 Outdoor unit error display
Display LED STATUS
IDU
Error
(Wall Mt.)
IDU
Error
(Others)
E0 Outdoor EEPROM malfunction
E5 E6
E2 Communication malfunction between indoor and outdoor units
E1 E2
E3 Communication malfunction between IPM board and outdoor main board
—— ——
E4 Open or short circuit of outdoor temperature sensor(T3、T4、TP、T2B)
E5 E6
E5 Voltage protection
P1 P0
E6 PFC module protection(Only for M4OC-36HRFN1-M)
—— ——
E8 Outdoor fan speed has been out of control(Only for DC fan motor models)
—— ——
F1 No A Indoor unit coil outlet temp. sensor or connector of sensor is defective
—— ——
F2 No B Indoor unit coil outlet temp. sensor or connector of sensor is defective
—— ——
F3 No C Indoor unit coil outlet temp. sensor or connector of sensor is defective
—— ——
F4 No D Indoor unit coil outlet temp. sensor or connector of sensor is defective
—— ——
P0 Temperature protection of compressor top (Only for M3OD-27HRDN1-M)
P2 P3(P1)
P1 High pressure protection (Only for M4OC-36HRFN1-M)
—— ——
P2 Low pressure protection(Only for M4OC-36HRFN1-M)
—— ——
P3 Current protection of compressor
—— ——(P2)
P4 Temperature protection of compressor discharge
—— ——
P5 High temperature protection of condenser
—— ——
P6 IPM module protection
P0 E5