EasyManua.ls Logo

Polaris PC 199-50 3NV - Gas Pressure Testing and Safety; Leak Testing Procedure; LP Gas Pressure Safety

Polaris PC 199-50 3NV
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
Gas Pressure Testing
Important: This water heater and its gas connection must
be leak tested before placing the appliance in operation.
If the code requires the gas lines to be tested at a
pressure of 14” W.C. (3.486 kPa) or greater, the water
heater and its manual shut-off valve must be discon-
nected from the gas supply piping system and the line
capped.
If the gas lines are to be tested at a pressure less
than 14” W.C. (3.486 kPa), the water heater must be
isolated from the gas supply piping system by closing
its manual shut-off valve.
Nationally listed/recognized fuel gas and carbon
monoxide(CO) detectors are recommended in
all applications and should be installed using the
manufacturers instructions and local codes, rules, or
regulations.
Note: Air may be present in the gas lines and could prevent
the burner from lighting on initial start-up. The gas lines
should be purged of air by a qualified service technician
after installation of the gas piping system.
Explosion Hazard
Have a qualified person make sure that
the L.P. gas operating pressure does not
exceed 13” water column (3.237 kPa).
Examples of a qualified person include
licensed heating personnel, authorized
gas company personnel, and authorized
service personnel.
Failure to do so can result in death,
explosion, or fire.

Related product manuals