10 4104 V100-UK
Order codes
4104 = Universal signal transmitter
4501 = Display / programming front
Specifications
Environmental conditions:
Specifications range .................................... -20°C to +60°C
Storage temperature ................................... -20°C to +85°C
Calibration temperature............................... 20...28°C
Relative humidity ......................................... <95%RH(non-cond.)
Protection degree ........................................ IP20
Installation in pollution degree 2 & measurement / overvoltage category II.
Mechanical specifications:
Dimensions (HxWxD) ................................... 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 display ........ 109 x 23.5 x 116 mm
Weight approx. ............................................ 250 g
DIN rail type ................................................. DIN EN 60715 - 35 mm
Wire size ...................................................... 0.13...2.08 mm
2
/
AWG 26...14 stranded wire
Screw terminal torque ................................. 0.5 Nm
Common electrical specifications:
Supply voltage, universal ............................ 21.6...253 VAC, 50...60 Hz
or 19.2...300 VDC
Power consumption .................................... ≤ 2.5 W
Internal power dissipation ........................... ≤ 2.0 W
Isolation voltage - test / working ................ 2.3 kVAC / 250 VAC
MTBF, acc. to IEC 61709 (SN29500) .......... >111years
Signal / noise ratio ...................................... >60dB
Cut-off frequency (3 dB) .............................. >40Hz
Response time (0...90%, 100...10%) .......... <20ms