12 5715V102-UK
Outputs:
Display:
Display readout ........................................... -1999...9999 (4 digits)
Decimal point .............................................. Programmable
Digit height .................................................. 13.8 mm
Display updating ......................................... 2.2 times / s
Input outside input range is
indicated by ................................................. Explanatory text
Current output:
Signal range (span) ...................................... 0...20 mA
Programmable signal ranges ...................... 0...20, 4...20,
20...0 and 20...4 mA
Load (max.) .................................................. 20 mA / 800 Ω / 16 VDC
Load stability ............................................... ≤ 0.01% of span / 100 Ω
Sensor error detection ................................ 23 / 0 / 3.5 mA / none
NAMUR NE 43 Up- / Downscale ................ 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals ............... 3,8...20.5 mA
on 0...20 and 20...0 mA signals ............... 0...20.5 mA
Current limit ................................................. ≤ 28 mA
Relay outputs:
Relay function.............................................. Setpoint
Hysteresis .................................................... 0...100%
On and Off delay ......................................... 0...3600 s
Sensor error detection ................................ Make / Break / Hold
Max. voltage ................................................ 250 VRMS
Max. current ................................................ 2 A / AC
Max. AC power ........................................... 500 VA
Max. current at 24 VDC............................... 1 A
Marine approval:
Det Norske Veritas, Ships & Offshore ......... Standard for Certification No. 2.4
GOST R approval:
VNIIM, Cert. no. ........................................... See www.prelectronics.com
Observed authority requirements: Standard:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 508