D
destinybatesJul 25, 2025
What to do if the air volume is not as specified in Price FDV Touch terminals?
- TTiffany OneillJul 25, 2025
To address air volume issues with your Price Touch terminals: 1. Inspect the filter for excessive dust accumulation. 2. Check the fan for any particle blockages. 3. Examine the coils for particle blockages. 4. Ensure downstream static pressure is at least 0.10 inches W.G. to prevent the fan from overheating. 5. Confirm the supply voltage matches the wiring diagram specifications, located inside the electrical enclosure or in the controls brochure. 6. Check for loose insulating duct liner. 7. Inspect for leaks or obstructions in the ductwork. 8. Ensure there are no sharp elbows near the fan outlet, and that turning vanes are properly designed.