10
8. Removing the Cover
Please Observe the Label on the Cover of the Actuator.
9. Setting of the Limit Switches
Only for deliveries without valves!
Two adjustable limit switches are installed to limit the stroke of the actuator, and cut-off the motor current in the
relative direction. (see 9.1 ff) Additional limit switches are free of voltage and serve to indicate the valve position.
Most motors have a thermal switch, depending on the actuator type, to cut off the current in both directions when a
maximum temperature is reached. The cover must be removed in order to set the limit switches.
PSL201-PSL210 (IP65)
Remove the handwheel by loosening it.
Pull the cover upwards.
PSL214 und PSL201-210 (IP67/IP68)
Remove the handwheel by loosening the grub screw.
Remove the fastening screws of the actuator cover.
Pull the cover upwards.
Figure 6: Removing the cover
PSL320 - PSL325 (IP65)
Remove the fastening screws of the actuator cover
Pull the cover upwards.
When mounting an actuator on a valve, never drive the actuator electrically but use the
handwheel. If these instructions are not observed, it may result in damage to the actuator
and/or valve.