CD10.241
CD-Series
DC/DC Converter 24V/24V, 10A, 240W
Sep. 2019 / Rev. 1.4 DS-CD10.241-EN All values are typical figures specified at 24Vdc input voltage 24V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/27
NVIRONMENT
-25°C to +70°C (-13°F to 158°F) The operational temperature is the ambient or
surrounding temperature and is defined as the
air temperature 2cm below the device.
-40°C to +85°C (-40°F to 185°F) For storage and transportation
-rating 3.2W/°C
6W/°C
15W/1000m or 5°C/1000m
9W/-5kPa or 3°C/-5kPa
Between +45°C and +60°C (113°F to 140°F)
Between +60°C and +70°C (140°F to 158°F)
For altitudes >2000m (6560ft), see Fig. 15-2
For atmospheric pressures <80kPa, see Fig. 15-2
The de-rating is not hardware controlled. The customer has to take care by himself to
stay below the de-rated current limits in order not to overload the unit.
5 to 95% r.h. According to IEC 60068-2-30
110-47kPa See Fig. 15-2 for details
See Fig. 15-2 for details
2 According to IEC 62477-1, not conductive
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
According to IEC 60068-2-6
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
According to IEC 60068-2-27
Shock and vibration is tested in combination with DIN-Rails according to EN 60715 with a
height of 15mm and a thickness of 1.3mm and standard orientation.
As a rule, only non-silicon precipitating materials are used. The unit conforms to the
LABS criteria and is suitable for use in paint shops.
Tested according to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke
Method 4 for a service life of minimum 10years in these environments.
se Some audible noise may be emitted from the power supply during no load, overload or
short circuit.
Fig. 15-1 Output current vs. ambient temp. Fig. 15-2 Output current vs. altitude at 24V
0
-25 0
20 40 70°C
2A
4A
6A
8A
10A
12A
60
Ambient Temperature
A... Continuous
B... Short term
A
B
Allowed Output Current at 24V
2000m 4000m
6000m
2A
4A
6A
8A
10A
12A
Altitude
Allowed Output Current at 24V
AP
*)
80kPa 62kPa 47kPa110kPa
0m
*) Atmospheric pressure
A... Ambient < 60°C
B... Ambient < 45°C
C... Short term
A
B
C