MICROPROCESSOR – BASED
WATER TREATMENT
CONTROLLER
Installation and Operation Manual

Questions and Answers

  • T
    Taylor Hays DDSAug 7, 2025
    What to do if my Pulsafeeder MICROtrac Control Systems controller displays "9999 Err"?
    • V
      Virginia MartinAug 7, 2025
      If your Pulsafeeder Control Systems controller powers up but displays "9999 Err", you can try resetting the limit by pressing the M (Mode) button when conductivity is back in range. Also check the probe wiring. If the problem persists, the conductivity probe may be faulty and require replacement.
  • A
    Andrew PhillipsAug 12, 2025
    Why does my Pulsafeeder MICROtrac Control Systems controller display "Lit Err"?
    • C
      Cynthia MccormickAug 12, 2025
      If your Pulsafeeder Control Systems controller powers up but displays "Lit Err", it could be due to the user-set Limit timer expiring. You can reset the limit by pressing the M (Mode) button. Alternatively, the conductivity may be over the maximum range, in which case you should reduce the system conductivity.
  • H
    Harry JohnsonAug 16, 2025
    What to do if my Pulsafeeder MICROtrac Control Systems controller displays "Flo Err"?
    • M
      Miss Ruth RobertsAug 16, 2025
      If your Pulsafeeder Control Systems controller powers up but displays "Flo Err", there are several potential causes. First, check or replace the fuse. Second, check the probe wiring. Third, check the flow switch connections. Fourth, the flow switch may be stuck, requiring cleaning of the flow sensor. Fifth, the flow switch cap may be faulty, so check for wire integrity or replace the flow cap. Finally, the shuttle may be bad, requiring replacement.
  • B
    brooksjessicaAug 20, 2025
    Why does my Pulsafeeder MICROtrac controller display "Cond Err"?
    • W
      wwhiteAug 20, 2025
      If your Pulsafeeder Control Systems controller powers up but displays "Cond Err", it could be due to a loose conductivity probe wire, so check the probe wiring. It could also indicate a bad conductivity probe, which would need to be replaced.
  • M
    Michelle ShawAug 25, 2025
    Why is the conductivity reading different on my Pulsafeeder MICROtrac Control Systems controller compared to my hand-held meter?
    • S
      Sarah GillespieAug 25, 2025
      Due to variations in hand-held meters, conductivity standard solutions, temperature compensation, and the controller’s accuracy of +/- 2% of scale, the conductivity reading on your Pulsafeeder Control Systems controller may not match that of your hand-held tester.
  • H
    Hannah JacksonAug 29, 2025
    How to fix insufficient flow through flow switch in Pulsafeeder Control Systems?
    • B
      Bradley HarrisAug 29, 2025
      If you have insufficient flow through the flow switch in your Pulsafeeder Control Systems, ensure there is enough of a pressure differential from the inlet of the flow switch and the outlet to achieve at least 1 GPM (3.8 LPM) of flow.
  • H
    Haley MckeeSep 2, 2025
    What to do if my Pulsafeeder MICROtrac Control Systems controller does not power up?
    • V
      Veronica MooreSep 2, 2025
      If your Pulsafeeder Control Systems controller does not power up, check the circuit breaker supplying power to the controller.