Pitched Towards Steam Generator
TM
Steam Supply Piping Examples
Notes:
1. Pitch hard piping or À exible hose 2” per foot if steam is À owing uphill, ¹»” per foot if the steam is À owing
downhill. Reference piping examples shown.
2. When feasible to do so, install a minimum one-foot riser from the top of the tank to reduce condensate carryover.
3. Use À ex connectors or unions to allow for easy removal of cover.
4. Support À exible hose every 18” to avoid sagging.
5. Hard piping or À exible hose must match reservoir outlet size. Do not use supply piping with a smaller inside diameter
than the reservoir outlet.
6. Failure to follow the piping recommendation on this page may result in blown water seals, leaking cover gasket, or
dispersion tubes spitting.
7. Install a Drain Tee at any low spots in supply piping run where condensate will accumulate. All horizontal to vertical
up transitions require a water-sealed drip leg.
8. Reference job speci¿ c tube assembly O&M included with your order for complete details.
Pitched Towards Tube Assembly
Pitched Towards Steam Generator
and Tube Assembly
Pitched Towards Drain Tee
Pitch
(see Note 1)
Use two 45° elbows for
hard piping or wide 90°
for À exible steam hose
Supply piping
connectors
(see Note 4)
Drain Tee
(see Note 7)
Typical
Humidi¿ er
Reservoir
see Note 2
see Note 2
see Note 2
see Note 2
2”/1’
2”/1’
2”/1’
¹»”/1’
¹»”/1’
¹»”/1’
9

Other manuals for Pure Humidifier EC-5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pure Humidifier EC-5 and is the answer not in the manual?

Pure Humidifier EC-5 Specifications

General IconGeneral
BrandPure Humidifier
ModelEC-5
CategoryHumidifier
LanguageEnglish

Related product manuals