) Press ‘Up’ and ‘Down’ to choose the setting item No., press ‘Enter’ to enter into the
detailed setting parameter, when finish press ‘Enter’ again. The following setting items
need to be set follow the recommended value:
Item No. Setting Value
Program 02 Set to N*25A, N=battery amount
Program 05 Set to USE
Program 12 Set to 48V
Program 13 Set to 51V
Program 26 Set to 53.2V
Program 29 Set to 47.5V
Note: WKS Inverter can only be waked up via battery, if the battery is turned off due to
over-discharge, over temp. or other reasons, in order to wake up the inverter you need
turn on the battery manually.
Any further questions to this SOP please contact us via service@pylontech.com.cn
Program 27
Set to 53V