CHARACTERISTICS AND INSTALLATION
GB
13
INSTALLATION SITE
Install the battery charger in a dry and ventilated place and as near to the batteries as possible. The
battery charger, although having high efficiency, develops a certain amount of heat during function-
ing, therefore, it is imperative that the installation area has sufficient ventilation, enough to allow use
of the equipment at maximum power.
The battery charger can be installed in a horizontal or vertical position with cables coming out in the
downward position. The vertical position is recommended because the natural convection of heat
helps to cool the equipment. The perimeter of the battery charger (except the base) must be kept at
a distance from walls or objects by a minimum of 5 cm.
FIG.1
The cables connected to the output terminals have a maximum length of 4 metres.
WARNING: the battery charger must be used only with a re-chargeable lead/liquid
electrolytic batteries or lead/gel (sealed or non-sealed).
WARNING: the outer surface of the battery charger is used as a heat sink, therefore it may
reach very high temperatures (risk of burns). Leave the equipment to cool down before
handling it.
MODEL
Battery voltage
Battery capacity
Minimum output cable size
SBC 100 ADV SBC 140 ADV SBC 250 ADV SBC 285 ADV
SBC 100 ADV DR SBC 140 ADV DR SBC 250 ADV DR SBC 285 ADV DR
12 V 24 V
35 ÷ 80 Ah 55 ÷ 120 Ah 110 ÷ 250 Ah 55 ÷ 120 Ah
4 mm
2
6 mm
2
10 mm
2
6 mm
2
EQUIPMENT REQUIRED FOR INSTALLATION
On the basis of the type of model, use the batteries and cables on the output terminals as specified