INSTALLATION DATA
ETC TWO STAGE ELECTRONIC
TEMPERATURE CONTROL
The Ranco® ETC is a microprocessor
based family of electronic temperature
controls, designed to provide on/o
control for commercial heang, cooling,
air condioning and refrigeraon. The ETC
is equipped with a liquid crystal display
(LCD) that provides a constant readout
of the sensed temperature, and a touch
keypad that allows the user to easily and
accurately select the setpoint temperature,
dierenal and heang/cooling mode
of the operaon. Models are available
that operate on either line voltage
(120/208/240V AC) or low voltage (24V AC).
APPLICATIONS
With its wide temperature setpoint range
and selectable heang or cooling modes,
the ETC can be used for a wide variety of
applicaons including mulple compressor
control, two stage heang, venlaon
control, automac changeover, condenser
fan cycling, space and return air tempera-
ture control, water cooled condensers and
control with alarm funcon.
FEATURES
Wide setpoint temperature range (-30°F to 220°F) and dierenal
adjustment (1°F to 30°F)
Simple keypad programming of setpoint temperature, dierenal and
cooling/heang modes
Two individually programmable stages for heang and/or cooling
LCD display readout of sensor temperature, control sengs, relay
status and onboard diagnoscs
LED (Light Eming Diode) backlight to improve visibility of the display
in low light ambient applicaons.
IP67 rated (water and dust resistant) thermistor-based probe to
remotely monitor temperature
The sensor probe can be retroed in the eld by the use of factory
installed interconnect
• Remote temperature sensing up to 400 feet
• Two SPDT output relays
• User-selectable Fahrenheit/Celsius scales
Lockout switch to prevent tampering by unauthorized personnel
• Choice of line voltage and low voltage models available
Oponal 0 to 10 volt analog output available for remote temperature
indicaon
An-short Cycle Compressor Delay for cooling applicaons
SPECIFICATIONS
Input Voltage 120 or 208/240V AC (24V AC oponal), 50/60 Hz
Temperature Range -30°F to 220°F
Dierenal Range 1°F to 30°F
Switch Acon SPDT
Sensor Thermistor, 1.94 in. long x 0.25 in. diameter
with 8 . cable, IP67 rated
Power Consumpon 120/208/240V AC: 100 milliamps
24V AC: 2-6V AC
1
Relay Electrical Rangs
NO Contact 120V 208/240V
Full-load amps 9.8 Amps 4.9 Amps
Locked rotor amps 58.8 Amps 29.4 Amps
Resisve amps 9.8 Amps 4.9 Amps
Horsepower 1/2 HP 1/2 HP
NC Contact
Full-load amps 5.8 Amps 2.9 Amps
Locked rotor amps 34.8 Amps 17.4 Amps
Resisve amps 5.8 Amps 2.9 Amps
Horsepower 1/4 HP 1/4 HP
Pilot Duty: 125 VA at 120/208/240 VAC
Control Ambient Temperature
Operang -20°F to 140°F (-29°C to 60°C)
Storage -40°F to 176°F (-40°C to 80°C)
Ambient Humidity 0 to 95%, RH, Non-condensing
0 to 10V Output Impedance 1 K
Enclosure NEMA 1, Plasc
Agency Approvals UL Listed, File E94419, Guide XAPX
CSA Cered, File LR68340, Class 4813 02
ETC ORDERING INFORMATION
Uni-Line OEM Input No. of 0 - 10 V
Numbers Numbers Voltage Stages Output
ETC-211000-000 ETC-211020-000 120/240 2 No
ETC-211100-000 ETC-211120-000 120/240 2 Yes
ETC-212000-000 ETC-212020-000 24 2 No
ETC-212100-000 ETC-212120-000 24 2 Yes
OPERATION
Liquid Crystal Display (LCD)
The LCD display provides a constant readout of the sensor temperature
and indicates if either of the two output relays is energized. When the
S1 annunciator is constantly illuminated during operaon, the Stage 1
relay is energized. Likewise, when the S2 annunciator is constantly
illuminated during operaon, the Stage 2 relay is energized. The display
is also used with the keypad to allow the user to adjust the setpoint
temperatures, dierenals and heang/cooling modes for each stage.
Backlight
When any mode key is pressed, the backlight is acvated and the ETC is
in control mode. Press the SET key to begin program mode.
Control Setup
The temperature setpoint refers to the temperature at which the
normally open (NO) contacts of the output relay will open. Determine
the loads to be controlled and the operang modes required for each
stage, cooling or heang.
When the cooling mode is chosen, the dierenal is above the setpoint.
The relay will de-energize as the temperature falls to the setpoint.
An-short Cycle Compressor Delay for cooling. Aer a relay
de-energizes, the ETC will prevent the relay from turning on unl a
congurable me has occurred to protect compressor.
When the heang mode is chosen, the dierenal is below the setpoint.
The relay will de-energize as the temperature rises to the setpoint.
The ETC two stage control can be set up for two stages of heang, two
stages of cooling or one stage cooling plus one stage heang. Refer to
Figures 1, 2 and 3 for a visual representaons of dierent control setups.

Questions and Answers:

Ranco ETC Series Specifications

General IconGeneral
DisplayLED
Control TypeOn/Off
OutputSPDT Relay
Accuracy±1°F (±0.5°C)
Enclosure RatingNEMA 1
Sensor TypeNTC Thermistor
Number of Outputs1
Temperature DifferentialAdjustable
MountingPanel
Input Voltage120/240V AC, 50/60Hz
Power Supply120/240V AC, 50/60Hz

Summary

Applications

Features

Setpoint and Differential Adjustment

Wide setpoint temperature range and adjustable differential.

Simple Keypad Programming

Easy selection of setpoint, differential, and heating/cooling modes.

Dual Stage Control

Two individually programmable stages for heating or cooling.

LCD Display and Backlight

Constant readout of temperature/settings and display backlight.

Durable and Remote Sensing Probe

IP67 rated thermistor probe for remote sensing up to 400 feet.

Additional Features

Includes SPDT relays, Fahrenheit/Celsius scales, lockout, optional output.

Specifications

Input Voltage and Power Consumption

Details input voltage options and power consumption.

Temperature and Differential Ranges

Defines operating temperature and differential ranges.

Switch Action and Sensor Type

Specifies switch action (SPDT) and NTC thermistor sensor.

Operating and Storage Conditions

Specifies control ambient temperature, storage, and humidity.

Ordering Information

Lists part numbers, voltage, stages, and analog output options.

Operation

Liquid Crystal Display (LCD)

Explains LCD function for temperature readout and settings.

Backlight

Describes backlight activation when keys are pressed.

Control Setup

Details how setpoint, differential, and modes are determined.

Anti-short Cycle Compressor Delay

Explains delay feature to protect compressors in cooling mode.

Programming Steps and Display Mode

Step 1: Fahrenheit/Celsius Mode

Select Fahrenheit or Celsius scale for temperature display.

Step 2: Stage 1 Setpoint

Set the desired temperature for Stage 1 operation.

Step 3: Stage 1 Differential

Set the differential for Stage 1 to control cycling.

Step 4: Stage 1 Cooling/Heating Mode

Select cooling (C1) or heating (H1) mode for Stage 1.

Step 5: Anti-short Cycle Compressor Delay

Configure the delay for compressor protection in cooling mode.

Step 6: Stage 2 Setpoint

Set the desired temperature for Stage 2 operation.

Step 7: Stage 2 Differential

Set the differential for Stage 2 to control cycling.

Step 8: Stage 2 Cooling/Heating Mode

Select cooling (C2) or heating (H2) mode for Stage 2.

Step 9: Programming Complete

Final step to confirm all programmed settings.

Lockout Switch

Lockout Switch Operation

How to use the lockout switch to prevent keypad tampering.

Troubleshooting Error Messages

Display Message E1

Error E1 indicates issue with key presses or control replacement.

Display Message E2

Error E2 signifies settings not stored, requiring correction.

Display Message EP

Error EP indicates probe issue (open, shorted, out of range).

Display Message EE

Error EE indicates EEPROM corruption, requiring control replacement.

Display Message CL

Error CL indicates calibration mode entry, requires power cycle.

Control Mounting

Mounting Instructions

Guidelines for mounting the ETC control to a flat surface.

Conduit Connections

Information on using 1/2 inch conduit connections and hub security.

Anti-Short Cycle Compressor Delay

Control Wiring

General Wiring Considerations

Conformity to NEC, load limits, copper conductors, slack for wiring.

Input and Output Wiring Diagrams

Diagrams for 24V AC and Line Voltage wiring.

Analog Output

Details the 0-10V analog output signal representation.

Field Repairs and Sensor Mounting

Field Repairs

Prohibits field calibration; recommends replacement controls.

Sensor Mounting

Guidelines for mounting sensor for space or spot sensing.

Extending Sensor Cable

Cable Extension Guidelines

How to extend sensor cable up to 400 feet using 22 AWG wire.

Checkout Procedure

Steps to verify installation and check sensor resistance.

Sensor Replacement

Quick Connect Sensor Feature

Explains easy sensor replacement using the Quick Connect feature.

Replacement Sensor Order Information

Provides part numbers for ordering replacement sensors.

Specifications: Sensor Resistance vs Temperature