Page #10 background image
Power Meter Quick Setup Guid
e
10
QSG
-PMM-1A-v3.3.10-E ļ‚Ÿ 255-64-0004-00
PMB Branch Circuit Wiring
A
CT plugs into 2-pin locking connector
(Molex 43640-0201)
B
Branch Circuits have two labels: Red
labels for odd/even numbered panels.
White labels for sequentially numbered
panels.
C
Multi-conductor CT cable. Available
lengths: 3m, 10m.
D
Connect labeled end into matching labeled
connector
All CTs 333mV output. DO NOT use current
output CT.
CT can be connected to live circuit in either
direction. Meter auto corrects polarity.
Branch Circuit
Description
Current Transformers
How Many
Connect To
Line-Neutral (LN) 120V/230V circuit wired to 1-pole circuit breaker 1 phase line
Line-Line (LL) 208/240/400V circuit wired to 2-pole circuit breaker 1 either phase line
Line-Line-Neutral (LLN) 120V+208/240V circuit wired to 2-pole circuit breaker 2 each phase line
Three-Phase (LLL, LLLN) 3-phase circuit wired to 3-pole circuit breaker 3 each phase line