CVS-21HA.rev.03 29
The alarm pilot light turns on when the alarm is activated.
HIGH ALARM
The controller activates the alarm when the room temperature rises above
the value set point+ high offset .
To adjust alarm high offset:
Set selection knob to ALARM OFFSET LOW. The current low
offset appears flashing on the display.
Using adjustment knob, adjust the offset to the desired value.
The low offset can be adjusted between 0.5
o
and 40.0
o
F (0.3° and
22.0°C).
LOW ALARM
The controller activates the alarm when the ambient temperature falls below
the value set point - low offset .
To adjust alarm low offset:
Set selection knob to ALARM
OFFSET HIGH. The current
high offset appears flashing on
the display.
Using adjustment knob, adjust the
offset to the desired value.
The high offset can be adjusted
between 0.5° and 40.0°F (0.3° and
22.0°C).
ALARMS
POWER FAILURE OR FAULT IN THE SUPPLY CIRCUIT
The controller activates the alarm in the event of a power failure or a fault
in the supply circuit.