29
MODE 5
(With Default Settings Shown)
ADJUST MENU
(Page 3 of 3)
I
tem Field Range Description
Setting
0:10 to 5:00 min
MINIMUM ON TIME
Select the minimum amount of time that
the stage contact must remain on before it
is allowed to turn o.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 5:00 min
MINIMUM OFF TIME
Select the minimum amount of time that
the stage contact must remain o before it
is allowed to turn back on.
Note: This setting is only available when
STAGE MODE is set to P.
OFF, 0:20 to
9:55 min, On
PUMP DELAY
Select the system pump purge time after
shutting o the burner.
35 to 100°F
(2 to 38°C),
OFF
WARM WEATHER SHUT DOWN
Select the heating system warm weather
shut down for outdoor reset operation. Heat
demands are ignored once the outdoor air
temperature exceeds this setting.
°F or °C
TEMPERATURE UNITS
Select to display temperature in degrees
Fahrenheit or in degrees Celsius.
Table O: Adjust Menu, Mode 5 (page 3 of 3)