MODBUS COMMUNICATIONS HeatNet Control V3
Page 124
MODBUS Input Variables (Read Only)
Address
Name
Raw Data
Type
Scale
Description
Valid Values/Range
30165
Boiler06Status4
30166
Boiler07Status4
30167
Boiler08Status4
30168
Boiler09Status4
30169
Boiler10Status4
30170
Boiler11Status4
30171
Boiler12Status4
30172
Boiler13Status4
30173
Boiler14Status4
30174
Boiler15Status4
30175
Boiler16Status4
30176
30207
RESERVED
---
---
---
---
30208
Boiler01DHWTemp
16 bit signed
---
Boiler (1 16) DHW temperature (if
available). See BoilerStatus4 to
32 250 °F
30209
Boiler02DHWTemp
30210
Boiler03DHWTemp
30211
Boiler04DHWTemp
30212
Boiler05DHWTemp
30213
Boiler06DHWTemp
30214
Boiler07DHWTemp
30215
Boiler08DHWTemp
30216
Boiler09DHWTemp
30217
Boiler10DHWTemp
30218
Boiler11DHWTemp
30219
Boiler12DHWTemp
30220
Boiler13DHWTemp
30221
Boiler14DHWTemp
30222
Boiler15DHWTemp
30223
Boiler16DHWTemp
30224
Boiler01Modulation
16 bit signed
---
The running (“display”) modulation. This is
typically the actual running modulation
except under special circumstances when
the boiler is running in a self-protection
mode (Op. Limit, ½ Fire Rate, etc.)
Boiler01 = Master or “Connected Boiler”
Boiler02 = Member01
Boiler16 = Member15
0 - 100
30225
Boiler02Modulation
30226
Boiler03Modulation
30227
Boiler04Modulation
30228
Boiler05Modulation
30229
Boiler06Modulation
30230
Boiler07Modulation
30231
Boiler08Modulation
30232
Boiler09Modulation