SPECIFICATIONS (Cont’d)
6. FRONT PANEL BUTTONS:
SELECT: Toggles display in the normal operating mode if enabled.
Advances menu selection in programming mode.
RESET: Resets counter to zero in the normal operating mode if enabled.
Changes data in programming mode.
7. COUNT DISPLAY: 8-digit with positive count, 7-digit with minus sign
indication for negative count and the display flashes “tot OVEr” for an
overflow condition. Dual count mode only, “B” counter, seven digit positive
count: “btot OVEr” appears for an overflow condition.
8. RATE DISPLAY: 6 digits with an annunciator “R” on the left hand side of
the LCD.
Overflow Indication: “R OLOLOL” appears when max. display digits are
exceeded.
9. RATE ACCURACY: 0.05%
10. RATE MINIMUM INPUT FREQUENCY: 0.01 Hz
11. RATE MAXIMUM FREQUENCY: 10 KHz
12. MAXIMUM COUNT RATES:
COUNTER RATE RATE
MODE
ENABLED DISABLED
cnt ud 10 KHz 20 KHz
rtE cnt 7.5 KHz 20 KHz
QUAd1 5 KHz 10 KHz
QUAd2 5 KHz 8 KHz
QUAd4 2.5 KHz 5 KHz
Add Add 7.5 KHz 10 KHz
Add Sub 7.5 KHz 10 KHz
dUAL cnt 7.5 KHz 10 KHz
13. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0 to 60°C (above 50°C, derate backlight operating
voltage to 24 VDC max.).
Storage Temperature: -30 to 85°C
Operating and Storage Humidity: 85% max. (non-condensing) from 0°C
to 50°C.
Altitude: Up to 2000 meters
14. CERTIFICATIONS AND COMPLIANCES:
SAFETY
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for
measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
Type 4X Enclosure Rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY
Refer to EMC Installation Guidelines for additional information.
15. CONSTRUCTION: High impact plastic case with clear viewing window.
The front panel meets NEMA 4X/IP65 requirements for indoor use when
properly installed. Installation Category I, Pollution Degree 2. Panel gasket
and mounting clip included.
16. WEIGHT: 3 oz (85 grams)
BASIC OPERATION
When power is applied to the unit, it performs an internal self-diagnostic test
and then the unit displays its revision level. If all P’s appear in the display, press
the select (SEL) button and check all of the data setups.
The CUB5 can be programmed to function as a single counter, dual counters,
single counter with rate indication or dual counters with rate indication.
Counter
The CUB5 receives incoming pulses and multiplies them by the Count Scale
Factor. The unit’s counter (internal count value) keeps track of the scaled input
pulse count which results in the desired reading value for the count display.
Input A accepts the signal for the count and Input B is used for quadrature, dual
counter, anti-coincidence counting, or up/down control counting.
The count(s) reset to zero when a manual reset is performed. At loss of power
to the unit, the contents of the counter are saved. This allows counting over
consecutive shifts, days, etc. The total count can accumulate to 99,999,999.
The “B” counter, if enabled, can accumulate 9,999,999 counts.
Note: The counter value will roll over and flash “tot OVEr” when the count
value exceeds 99,999,999, indicating an overflow condition. The “B”
counter, if enabled, will roll over and flash “btot OVEr” when the count
exceeds 9,999,999.
Rate
The signal at Input A is for the Rate indicator, which uses a time interval
method (1/tau) to calculate the rate value. The unit counts on the negative edge
of the input pulses. After the programmed minimum update time elapses and
the next negative edge occurs, the unit counts the number of edges that occurred
during the elapsed time. The number of edges is multiplied by the rate scaling
value to calculate the rate value. At slower rates, averaging can be
accomplished by programming the rate minimum update time for the desired
response. Extensive scaling capabilities allow practically any desired reading
at very slow count rates.
DISPLAY SELECTION
In the normal operating mode the program terminal is not connected to
common. The display indicates either:
Rate value designated by an “R” to the left of the display,
“A” count value (no designator), or
“B” count value designated by a “b” to the left of the display
If the Select button is enabled, the display may be toggled by pressing the
select button. If display scroll is enabled, the display will toggle automatically
approximately every four seconds between the rate and count values. If both
the select button and display scroll are enabled, pressing and holding the select
button pauses the automatic toggle (if enabled) as long as the select button is
held.
BLOCK DIAGRAM
900 MHz ± 5 MHz
Immunity to EN 50082-2
200 Hz, 50% duty cycle
Simulation of cordless telephone ENV 50204 Level 3; 10 V/m
Electrostatic discharge EN 61000-4-2 Level 2; 4 Kv contact
Level 3; 8 Kv air
Electromagnetic RF fields EN 61000-4-3
Level 3; 10 V/m
1
80 MHz - 1 GHz
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms
150 KHz - 80 MHz
Emissions to EN 50081-2
RF interference EN 55011 Enclosure class A
Power mains class A