MODEL NO. DESCRIPTION PART NUMBERS
CUB5 Dual Counter & Rate Indicator Positive Image Reflective CUB50000
Dual Counter & Rate Indicator w/Yel-Grn Backlighting CUB50010
Dual Counter & Rate Indicator w/Red Backlighting CUB50020
MLPS Micro Line/Sensor Power Supply MLPS0000
For more information on Pricing, Enclosures & Panel Mount Kits refer to the RLC Catalog or
contact your local RLC distributor.
ORDERING INFORMATION
APPLICATION
A dairy producer wishes to indicate the flow rate and record the total
gallons of milk dispensed from its processing tank. The CUB5 is installed to
meet these requirements.
A PSAC is used to sense a bolt head attached to the shaft of the pump. This
results in 32 pulses per gallon dispensed and the counter displays the total
gallons in tenths.
The pump typically dispenses 15.0 gallons per minute and the rate display
is to indicate tenths of gallons per minute (GPM). The front panel reset button
is disabled to prevent unauthorized reset of the total. An external key switch
is used for the reset function and the display select button is enabled to allow
viewing of either the rate or the total count.
PROGRAMMING:
INP A-b = cnt ud
dSPSEL = YES
totrst = NO
dSPScroL = NO
USEr INP = rESEt
Count Display Set-up:
tot dP = 0.0
SCLFAC =
Desired Display Units
x Decimal Point Position
Number of Pulses
=
1.0
x 10
32
= 0.3125
Rate Display Set-up:
rAtE ENb = YES
rAtE dP = 0.0
rAtE dPS = 15.0 GPM
rAtE INP = rAtE dSP x
pulses per unit
desired time format
= 15.0 x
32
60
= 8.0 Hz
Lo-Udt = 1.0 sec.
Hi-Udt = 5.0 sec.
TROUBLESHOOTING