Operating and Storage Humidity: 80% maximum relative humidity (non-
condensing) from 0 to 50°C.
Vibration according to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction for 1.5 hours, 2 g’s.
Shock according to IEC 68-2-27: Operational 35 g’s, 9 msec in 3 directions.
Altitude: Up to 2000 meters.
9. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010-1, CSA 22.2 No.61010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File #E211967, UL61010-1, ANSI/ISA 12.12.01-2007, CSA 22.2
No. 61010.1, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/12460C/UL,
CB Scheme Test Report #E179259-A1-CB-1
Issued by Underwriters Laboratories Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP66 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.
Immunity to Industrial Locations:
1. POWE
REQUIREMENTS:
Must use Class 2 or SELV rated power supply.
Power connection via removable three position terminal block.
Supply Voltage:
Typical Power
1
:
Maximum Power
2
:
Notes:
1. Typical power
+24 VDC ±20%
27 W
67 W
with +24 VDC, RS232/485 communications, Ethernet
communications, CompactFlash card installed, and display at full brightness.
2. Maximum power indicates the most power that can be drawn from the
G315C. Refer to “Power Supply Requirements” under “Installing and
Powering the G315C.”
3. The G315C’s circuit common is not connected to the enclosure of the
unit. See “Connecting to Earth Ground” in the section “Installing and
Powering the G315C.”
4. Read “Power Supply Requirements” in the section “Installing and
Powering the G315C” for additional power supply information.
2. BATTERY: Lithium coin cell. Typical lifetime of 10 years.
3. LCD DISPLAY:
Electrostatic discharge EN 61000-4-2 Criterion A
4 kV contact discharge
8 kV air discharge
Criterion B
10 V/m
Criterion B
2 kV power
1 kV signal
Criterion A
1 kV L-L,
2 kV L&N-E power
Criterion B
3 V/rms
*Lifetime at room temperature. Refer to “Display” in “Software/Unit Operation”
4. 10-KEY KEYPAD: for on-screen menus.
5. TOUCHSCREEN: Resistive analog
6. MEMORY:
On Board User Memory: 32 Mbyte of non-volatile Flash memory.
Electromagnetic RF fields EN 61000-4-3
Memory Card: CompactFlash Type
CompactFlash cards.
7. COMMUNICATIONS:
II slot for Type I and Type II
Fast transients (burst) EN 61000-4-4
USB Device Port: Adheres to USB 2.0 Specification supporting high speed
and full speed via Type B connection.
Surge EN 61000-4-5
RF conducted interference EN 61000-4-6
Emissions:
Emissions
Note:
EN 55011 Class A
Serial Ports: Format and Baud Rates for each port are individually software
programmable up to 115,200 baud.
PGM Port: RS232 port via RJ12.
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12.
DH485 TXEN: Transmit enable; open collector, V
OH
= 15 VDC,
V
OL
= 0.5 V @ 25 mA max.
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self
recovers.
10. CONNECTIONS: Compression cage-clamp terminal block.
Wire Gage: 12-22 AWG copper wire
Torque: 5-7 inch-pounds (56-79 N-cm)
11. CONSTRUCTION: Steel rear metal enclosure with NEMA 4X/IP66
aluminum front plate for indoor use only when correctly fitted with the gasket
provided. Installation Category II, Pollution Degree 2.
12. MOUNTING REQUIREMENTS: Maximum panel thickness is 0.25" (6.3
mm). For NEMA 4X/IP66 sealing, a steel panel with a minimum thickness of
0.125" (3.17 mm) is recommended.
Maximum Mounting Stud Torque: 17 inch-pounds (1.92 N-m)
13. WEIGHT: 11.41 lbs (5.17 Kg)
Note: For additional information on the communications or signal
common and connections to earth ground please see the “Connecting to
Earth Ground” in the section “Installing and Powering the G315C.”
Port to port isolation: 500 Vrms for 1 minutes signal isolation : 50V
Ethernet Port: 10 BASE-T / 100 BASE-TX
RJ45 jack is wired as a NIC (Network Interface Card).
Isolation from Ethernet network to G3 operator interface: 1500 Vrms
8. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50 °C
Storage Temperature Range: -20 to 70 °C
2
DIMENSIONS In inches (mm) 2.8
(71.5)
16.00 (406.4)
.28
14.59 (370.6)
(7.1)
13.00
(330.2)
11.59
(294.4)
PROTECTIVE EARTH GROUND
WARNING - DO NOT CONNECT OR DISCONNECT CABLES WHILE
POWER IS APPLIED UNLESS AREA IS KNOWN TO BE NON-
HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
SIZE 15-inch
TYPE TFT
COLORS
32K
PIXELS 1024 X 768
BRIGHTNESS 600 cd/m
2
BACKLIGHT* 50,000 HR TYP.
SPECIFICATIONS