9
Order codes
IAMS0001 Universal transmitter with analog output
IAMS0011 Universal transmitter with analog output / 2 relays
IAMS0010 Universal limit switch with 2 relays
PGMMOD00 Display / programming module
Electrical specifications
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, universal ............................ 21.6...253 VAC,
or 19.2...300 VDC
Max. consumption....................................... 2.5 W
Fuse ............................................................. 400 mA SB / 250 VAC
Isolation voltage, test / operation ............... 2.3 kVAC / 250 VAC
Communications interface .......................... Programming front PGMMOD00
Signal / noise ratio ...................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%):
Temperature input ................................... 1 s
mA / V input ............................................ 400 ms
Calibration temperature............................... 20...28°C
Display resolution: The temperature display automatically changes to tenths
with values less than 1000 degrees.
Accuracy, the greater of the general and basic values:
General values
Input
type
Absolute
accuracy
Temperature
coefficient
All ±0.1% of span ±0.01% of span / °C