-46-
Drawing No. LP0932 Released 2018-01-12
REGISTER
(4x)
REGISTER NAME LOW LIMIT HIGH LIMIT
FACTORY
SETTING
ACCESS COMMENTS
119 Control Mode Transfer Access 2 3 2 Read/Write 2 = HIdE, 3 = LOC
120 Deviation Value Access 0 3 0 Read/Write 0 = dISP, 3 = LOC
121 Access Code -125 125 0 Read/Write
0 = Full access to display, parameter, hidden, and
configuration loops; -1 to -125 = Code necessary to
access configuration loop only; 1 to 125 = Code
necessary to access hidden and configuration loops
122 CT1 Access 0 3 0 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC
123 Profile Status Access 0 4 1 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
124
Profile Segment Time Remaining
Access
0 4 1 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
125 Starting Profile Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
126 Starting Segment Access 1 3 3 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
127 Setpoint Mode Access 2 3 3 Read/Write 2 = HIdE, 3 = LOC
128 Profile Running Indicator Access 0 3 0 Read/Write 0 = dISP, 3 = LOC
ALARM PARAMETERS
131 Alarm 1 Action 0 17 0 Read/Write
0 = NONE, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = PErt,
10 = Ct1, 11 = HoLd, 12 = rPuP, 13 = rPdn, 14 = run,
15 = PAUS, 16 = StoP, 17 = End
132 Alarm 1 Annunciator 0 1 0 Read/Write 0 = Nor, 1 = REv
133 Alarm 1 Reset Mode 0 1 0 Read/Write 0 = Auto, 1 = LAtc
134 Alarm 1 Standby 0 1 0 Read/Write 0 = NO, 1 = yES
135 Alarm 1 Value -999 9999 1000 Read/Write 1 = 1 Display unit
136 Input Fail Alarm 1 Action 0 1 0 Read/Write 0 = OFF; 1 = On
137 Alarm 2 Action 0 17 0 Read/Write
0 = NONE, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = PErt,
10 = Ct1, 11 = HoLd, 12 = rPuP, 13 = rPdn, 14 = run,
15 = PAUS, 16 = StoP, 17 = End
138 Alarm 2 Annunciator 0 1 0 Read/Write 0 = Nor, 1 = REv
139 Alarm 2 Reset Mode 0 1 0 Read/Write 0 = Auto, 1 = LAtc
140 Alarm 2 Standby 0 1 0 Read/Write 0 = NO, 1 = yES
141 Alarm 2 Value -999 9999 2000 Read/Write 1 = 1 Display unit
142 Input Fail Alarm 2 Action 0 1 0 Read/Write 0 = OFF; 1 = On
143 Alarm 3 Action 0 17 0 Read/Write
0 = NONE, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = PErt,
10 = Ct1, 11 = HoLd, 12 = rPuP, 13 = rPdn, 14 = run,
15 = PAUS, 16 = StoP, 17 = End
144 Alarm 3 Annunciator 0 1 0 Read/Write 0 = Nor, 1 = REv
145 Alarm 3 Reset Mode 0 1 0 Read/Write 0 = Auto, 1 = LAtc
146 Alarm 3 Standby 0 1 0 Read/Write 0 = NO, 1 = yES
147 Alarm 3 Value -999 9999 3000 Read/Write 1 = 1 Display unit
148 Input Fail Alarm 3 Action 0 1 0 Read/Write 0 = OFF; 1 = On
149 Alarm Hysteresis 0
250(.0)° or
2500 (process)
10 Read/Write
1 = 1 Display unit; The same value applies to all
alarms.
150 Change Color Intensity 0 4 0 Read/Write
0 = OFF, 1 = Any Alarm, 2 = AL-1, 3 = AL-2,
4 = AL-3
171 SP1 Access 0 3 0 Read/Write 0 = dISP, 1 = PArA, 2 = HIdE, 3 = LOC
172 SP2 Access 0 3 3 Read/Write 0 = dISP, 1 = PArA, 2 = HIdE, 3 = LOC
SERIAL COMMUNICATION PARAMETERS
211 Communications Type 0 1 1 Read/Write 0 = ASCII, 1 = rtU
212 Baud Rate 0 4 4 Read/Write 0 = 2400, 1 = 4800, 2 = 9600, 3 = 19200, 4 = 38400
213 Data Bit 7 8 1 Read/Write 0 = 7,1 = 8
214 Parity Bit 0 2 0 Read/Write 0 = No, 1 = Even, 2 = Odd
215 Unit Address 1 247 247 Read/Write