— English Reflex Fillsoft — 12.05.2015
Fittings
Fitting Fitting group
Type Fitting Fitting group
Recommended range of application in heating
systems
20 kW – 300 kW 301 kW – 600 kW
Length 260 mm 380 mm
Width 130 mm 130 mm
Height 600 mm 600 mm
Weight 3.0 kg 5.8 kg
Permissible gauge operating pressure 8 bar 8 bar
Permissible operating temperature 5 °C – 40 °C 5 °C – 40 °C
Connections, inlet/outlet Internal thread Rp ½ Internal thread Rp ½
Maximum continuous flow rate 0,4 m
3
/h
0,4 m
3
/h
Calculating the cartridge capacity
Use the regional overall water hardness to calculate the cartridge's capacity to treat the water. The cartridge must be replaced when this
capacity is reached.
Cartridge capacity for treating water
Fillsoft Zero for desalinating
Capacity with one cartridge
• Fillsoft 1
6,000 [litres x °dH] 3,000 [litres x °dH]
Overall water
hardness [°dH]
Overall water hardness [°dH]
Capacity with two cartridges
• Fillsoft 2
12,000 [litres x °dH] 6,000 [litres x °dH]
Overall water
hardness [°dH]
Overall water hardness [°dH]
To calculate the soft water capacity, you require the value of the relevant regional overall water hardness [°dH].
– Degree of German water hardness [°dH].
Contact the local water supplier for the regional overall water hardness.
– Optionally use the measuring equipment for determining the regional overall water hardness.