— English Reflex Fillsoft — 12.05.2015
Caution – risk of injury!
• If installation, removal or maintenance work is not carried out correctly, there is a risk of injuries at the connection
points, if pressurised water suddenly escapes.
– Ensure proper installation, removal or maintenance work.
– Ensure that the system is de-pressurised before performing installation, removal or maintenance work at the
connection points.
Caution – Risk of injury due to falls or bumps!
• Bruising from falls or bumps at system components during installation.
– Wear personal protective equipment (helmet, protective clothing, gloves, safety boots).
Caution – risk of burning!
• Excessively hot surfaces in heating systems can cause burns on the skin.
– Wear protective gloves.
– Please place appropriate warning signs in the vicinity of the device.
For maintenance, proceed as follows:
• Check the cartridge capacity at least every six months. To check the capacity use the actual water level or the water level entry in the
machine log before installation.
• Replace the cartridge when 90 % of the capacity is spent.
• Replace the cartridge at the latest after 18 months.
• Dispose of the spent cartridge with normal household waste.