INSTRUCTION
i
Read this instruction before installation
and wiring of the product
OPTIGO OP10
Consult documentation in all cases where this symbol
is used, in order to nd out the nature of the potential
hazards and any actions to be taken
1
OPTIGO OP10, OP10-230
Controller with display
Optigo OP10 is a pre-programmed, congurable controller. It has
10 inputs/outputs and can be congured to control temperature
(ventilation control with heating and cooling), water-heated radiator
heating with outdoor temperature dependent control-curve or
domestic hot water control.
From revision R20, it is possible to connect an external setpoint
device. The device can be used for control modes 1-4.
OP10 is available in two versions, OP10 with 24 V AC supply voltage
and OP10-230 with 230 V AC supply voltage.
All conguration and normal handling is done using the display and
the knob on the front.
Technical data
Supply voltage
OP10-230 230 V AC +10/-15%, 50/60 Hz
OP10 24 V AC ±15%, 50/60 Hz
Power consumption 4 VA
Ambient temperature 0...50°C
Ambient humidity Max. 95% RH
Storage temperature -20...70°C
Display Numeric / graphic. Background
illumination.
Inputs Refer to connection illustrations and table
below
Terminal blocks Disconnectable, so-called lift type for cable
cross-section 2.5 mm
2
Protection class IP20
Material, casing Polycarbonate, PC
Weight
OP10-230 370 g incl. terminals
OP10 215 g incl. terminals
Dimensions 122 x 120 x 64 mm (WxHxD incl. terminals)
Overvoltage category 3
Pollution degree 2
Inputs
AI Resolution: 10 bit A/D
AI1 PT1000-sensor, range 5…80°C
AI2 PT1000-sensor, range -30…+50°C
SPI PT1000 setpoint device, range 0…40°C
UI
AI PT1000, range 0…80°C
or DI Closing potential-free contact
A
GND
Reference for AI
UI+ Reference for UI
DI Closing potential-free contact
DI+ Reference for DI
Outputs
AO 0…10 V DC; 8 bit D/A short-circuit protected
DO1 and DO2
(OP10) Triac controlled, 24 V AC, 0.5 A continuous (connected
to G0)
DO1 and DO2
(OP10-230) Triac controlled, 24 V AC, 0.16 A continuous with
internal trafo (connected to G0)
DO3 Change-over (SPDT) relay 230 V AC, 1000 VA
GDO Reference for DO1 and DO2. 24 V AC output
Setpoint values
Temperature Factory setting
Supply air 10...80°C 21°C
Cascade control, room 10...50°C 21°C
Radiator circuit control 10...40°C 21°C
(only when using
a room sensor)
External setpoint 0...40°C
Domestic hot water 10…80°C 55°C
Neutral zone 0...10°C 1°C
P-band 0…99°C 15°C
I-time 0…990 s 60 s
D-factor 0…99 0
P-band cascade 0.5…99°C 15°C
Min. at cascade 0…99°C 15°C
Max. at cascade 0…99°C 25°C
Damper min. limit 0…99 % 10 %
Start of outdoor compens. -30…50°C 10°C
Outdoor compensation
at -20°C outdoor temp. -10…10°C 5°C
Supply temperature
(water-heated radiator
heating)
at -20°C outdoor temp. 0…99°C 60°C
at 20°C outdoor temp. 0…99°C 20°C
Frost protection 7°C (xed)
SP. Shutdown mode 25°C (xed)
Actuating time,
3-point actuator 10...300 s 120 s
Frost protection thermo-
stat heating output 0...100 % 25 %
Installation
OP10-230 must be installed in a casing (DIN-casing or similar) where
it can be used without risk of electric shock and where it fullls the
demands for the LVD-standard. See the section Installation in the
“Optigo OP10 Manual”, which can be downloaded from www.regin-
controls.com.
Disconnection
The controller PO10-230 shall be connected to a switch or circuit
breaker in the building installation. This switch shall be in close prox-
imity to the controller and within easy reach of the operator, and shall
be marked as the disconnecting device for the equipment.
6762L
OCT 13
EN

Other manuals for Regin OPTIGO OP10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Regin OPTIGO OP10 and is the answer not in the manual?

Regin OPTIGO OP10 Specifications

General IconGeneral
BrandRegin
ModelOPTIGO OP10
CategoryNetwork Router
LanguageEnglish

Related product manuals