INSTRUCTION
i
Read this instruction before installation
and wiring of the product
TTC40F
Consult documentation in all cases where this symbol
is used, in order to nd out the nature of the potential
hazards and any actions to be taken
1
TTC40F
Triac controller for proportional control
of electric heating
TTC40F is a proportional controller for electric heating with automatic
voltage adaption. TTC40F pulses the whole load On - Off. The ratio
between On-time and Off-time is varied 0 - 100% to suit the prevailing
heat demand. The current is always switched at zero phase angle to
prevent RFI.
TTC40F can control both symmetrical Y-connected 3-phase heaters
and symmetrical or asymmetrical Delta-connected heaters.
TTC40F is only intended for electric heating control. The control prin-
ciple makes it unsuitable for motor- or lighting control.
TTC40F is intended for DIN-rail mounting.
Installation
Mount TTC40F on a DIN-rail in a cabinet or other enclosure.
Mount TTC40F vertically with the text right side up.
Protection class: IP20.
Ambient temperature: 0 - 40°C
N.B. TTC40F emits approx. 70W of heat at full output which must be
dissipated.
Wiring
Supply voltage
Terminals L1in, L2in and L3in.
Supply voltage: 210-255 or 380-415V AC
3 phase, 50 - 60 Hz with automatic voltage adaption.
Maximum current 40A/phase.
N.B. The supply voltage to TTC40F should be wired via an all-pole switch
with a minimum contact gap of 3mm.
N.B. TTC40F must be earthed.
1
1
1
3
2 3
4 5 6
7
8
9
L1
L2
L3
L3
L2
L1
Figure 1: Wiring of supply voltage and load
Load
Terminals L1out, L2out and L3out.
Resistive 3-phase heater without neutral
Maximum load: 5290W/phase at 230V phase - phase voltage (40A).
9200W/phase at 400V phase - phase voltage (40A).
Minimum load: 530W/phase at 230V phase - phase voltage (4A).
920W/phase at 400V phase - phase voltage (4A).
Main sensor and external set-point (gs 2-6)
Terminals 1and 4. Low voltage. Not polarity sensitive.
N.B. Terminals 2 and 3 are internally connected and are used to simplify
wiring when using external setpoint.
N.B. Choice of internal or external setpoint is done using switch 1.
1779F
MAR 14
EN
Figure 2: Wiring of room sensor TG-R530 or TG-R6xx when using
internal setpoint
1
2
TG-K3xx
TG-G1xx
3 4
12
3
2
TG-K3xx
TG-G1xx
TG-R4xx
3 4
12
2
1
TG-K3xx
TG-G1xx
TBI-xx
3
4
Figure 6: Wiring of external, separate sensor when using
potentiometer TBI-xx as external setpoint
Figure 3: Wiring of room sensor TG-R430 used as external
setpoint and sensor
Figure 4: Wiring of oor or duct sensor when using
internal setpoint
Figure 5: Wiring of external separate sensor when using TG-R4xx