CORRIGO C10-LON
INSTRUCTION
Corrigo C10-LON is a controller primarily intended
for controlling air handling units. It can easily be
adapted to suit different types of units.
Corrigo C10-LON has built-in capability for LON
communication. See separate LON interface manual.
Corrigo C10-LON has three 0...10 V DC control outputs
in sequence for controlling for example heating / heat
exchanger / cooling.
It has a number of functions and possibilities, such as
DX-cooling in one or two steps, outdoor temperature
compensation, fire damper exercise, control and
monitoring of fans and circulation pump, free cooling,
heat-exhanger efficiency calculation etc.
Corrigo C10-LON can also receive and handle a number
of alarms such as fan and filter alarm, smoke alarm,
chiller alarm, heat-exchanger alarm and has a free relay
output for total alarm.
Corrigo C10-LON has a year-base real-time clock,
week-scheduler , holiday calendar, holiday periods and
automatic normal time/daylight saving time change-over.
Installation
Mount the unit on a DIN rail in a cabinet or separate
enclosure.
For mounting in the cabinet front, use mounting kit FMC.
Degree of protection IP20
Ambient temperature 0...50°C
Wiring
Supply voltage
Terminals 42 and 43: 24 V AC, ±15%, 50/60 Hz.
Sensors AI3...AI8
Use PT1000 sensors. (See data sheet 4-150).
The choice of which sensors to connect is determined by
the choice of functions. The table, fig 3 can be used as
an aid in determining which sensors to install.
Connect the sensors according to the terminal schema-
tics on page 6.
N.B. All AI-inputs must refer to the signal neutral termin-
als for AI-inputs (terminals 24, 27, 30, 33).
AI4 has different functions depending on settings.
1. Efficiency calculation - exhaust air sensor.
2. Liquid-connected heat exchanger - limiting sensor in
the exchanger circulation system.
3. External setpoint. Input for setpoint signal.
These functions are mutually exclusive.
Only one of them may be chosen.
AI8 is, depending on setting, used for:
1. Frost protection sensor for applications with water
heated heater.
2. High temperature limiting switch for applications with
electrical heater.
When used for high temperature limiting switch it must be
connected to a free contact closing on alarm.
Fan supervision,
supply air fan, exhaust air fan AI1, AI2
Connect AI1 and AI2 to free contacts that open when the
fans stop.
Either in form of pressure switches monitoring the
pressure over each fan or as free contacts in the fan
motor relays.
N.B. Since these signals control vital functions they must
be connected for the unit to work as intended.
Digital inputs DI1...DI8
The digital inputs DI1...DI8 must refer to terminal 22.
N.B. Terminal 22 must not be connected to any other
terminals but should only be used as reference for units
connected to DI1...DI8.
The inputs may only be connected to potential free
contacts.
Closed contact activates alarm or function.
Unused inputs are to be left open.
DI1 Input for filter guards
DI2 Input for circulation pump indication.
Must be connected for systems with water heating.
DI3 Input for chiller alarm
DI4 Input for rotation sentinel or ice build-up sentinel for
heat exchanger.
DI5 Input for smoke alarm.
DI6 Input for fire damper end-position indication, external
alarm or external switches ”not in Auto position”.
(See textblock on DO6/DI6 on page 6).
DI7 Input for start of extended running time for single
speed fan systems or high speed for two speed fan
systems.
DI8 Input for start of extended running time at low speed
for two speed fan systems
DI7 and DI8 should, depending on settings, either be
wired to a momentarily closing pushbutton or to, for
example, a timer.
If DI7 and DI8 are both closed at the same time the unit is
shut down.
If a separate handswitch for setting the running mode is
installed it should be wired according to figure 1 or 2.
!
IMPORTANT: Read these
instructions before installation
and wiring of the product.
1-speed fans 2-speed
INSTRUCTION 1
ð
Fig 3
Fig 1
High
Low
0
Auto
DI7
DI8
H
0
Auto
DI8
DI7
Fig 2
Tel:+46 (0)31 795 44 60 Fax:+46 (0)31 795 38 50
Box 116
428 22 KÅLLERED, SWEDEN
Question and Answer IconNeed help?

Do you have a question about the Regin Corrigo C10-LON and is the answer not in the manual?

Summary

CORRIGO C10-LON Installation and Wiring

Al8 Sensor Configuration Options

Configuration for Al8 sensor: frost protection or high temperature limiting.

Fan Supervision Inputs (Al1, Al2)

Connecting Al1, Al2 for fan supervision to ensure proper system operation.

Digital Input Functions (DI1-DI8)

Details on using digital inputs DI1-DI8 for various system functions.

CORRIGO C10-LON Control Outputs and Display Navigation

Analogue and Digital Output Specifications

Specifications for analogue (AO1-AO3) and digital (DO1-DO7) control outputs.

Display Menu Tree and User Interface

User guide for display navigation, menus, and parameter adjustments.

System Login Levels and Access Control

Understanding the four login levels and their access privileges for system configuration.

CORRIGO C10-LON Configuration and User Login

User Login and Access Code Management

Steps for logging in, changing access codes, and managing security levels.

Configuration Menu Structure (A-S)

Overview of the configuration menu pages A through S for system setup.

Analogue Output Sequence Configuration (Y1, Y2, Y3)

Configuring the sequence and function for analogue outputs Y1, Y2, and Y3.

CORRIGO C10-LON Advanced Configuration Features

DX Cooling and Cooling Recovery Settings

Configuration options for DX cooling stages and cooling recovery functionality.

Free Cooling and DI6;DO6 Functionality

Settings for free cooling operation and combined DI6/DO6 input/output functions.

Temperature Control Parameter Adjustments

Adjusting setpoints, compensations, and limits for precise temperature control.

CORRIGO C10-LON System Operation and Alarms

Running Mode Selection and Monitoring

How to select and monitor the system's operational mode.

Scheduler and Holiday Period Setup

Setting up the weekly scheduler, holidays, and specific running periods.

Alarm Settings and Output Blocking Configuration

Configuring sensor alarms, alarm delays, and blocking of alarm output relays.

CORRIGO C10-LON DO6;D16 Functions and Configuration Codes

DO6;D16 Input;Output Functionality Details

Configuring DO6/D16 for frost alarm, external alarm, or fire damper exercise.

Configuration Codes and Factory Defaults

Overview of configuration codes for system setup and factory default values.

CORRIGO C10-LON Configuration Code Schematics

Configuration Code 1 (Functions A-L)

Detailed explanation of Configuration Code 1 for functions A through L.

Configuration Code 2 (Functions M-S)

Detailed explanation of Configuration Code 2 for functions M through S.

Summary

CORRIGO C10-LON Installation and Wiring

Al8 Sensor Configuration Options

Configuration for Al8 sensor: frost protection or high temperature limiting.

Fan Supervision Inputs (Al1, Al2)

Connecting Al1, Al2 for fan supervision to ensure proper system operation.

Digital Input Functions (DI1-DI8)

Details on using digital inputs DI1-DI8 for various system functions.

CORRIGO C10-LON Control Outputs and Display Navigation

Analogue and Digital Output Specifications

Specifications for analogue (AO1-AO3) and digital (DO1-DO7) control outputs.

Display Menu Tree and User Interface

User guide for display navigation, menus, and parameter adjustments.

System Login Levels and Access Control

Understanding the four login levels and their access privileges for system configuration.

CORRIGO C10-LON Configuration and User Login

User Login and Access Code Management

Steps for logging in, changing access codes, and managing security levels.

Configuration Menu Structure (A-S)

Overview of the configuration menu pages A through S for system setup.

Analogue Output Sequence Configuration (Y1, Y2, Y3)

Configuring the sequence and function for analogue outputs Y1, Y2, and Y3.

CORRIGO C10-LON Advanced Configuration Features

DX Cooling and Cooling Recovery Settings

Configuration options for DX cooling stages and cooling recovery functionality.

Free Cooling and DI6;DO6 Functionality

Settings for free cooling operation and combined DI6/DO6 input/output functions.

Temperature Control Parameter Adjustments

Adjusting setpoints, compensations, and limits for precise temperature control.

CORRIGO C10-LON System Operation and Alarms

Running Mode Selection and Monitoring

How to select and monitor the system's operational mode.

Scheduler and Holiday Period Setup

Setting up the weekly scheduler, holidays, and specific running periods.

Alarm Settings and Output Blocking Configuration

Configuring sensor alarms, alarm delays, and blocking of alarm output relays.

CORRIGO C10-LON DO6;D16 Functions and Configuration Codes

DO6;D16 Input;Output Functionality Details

Configuring DO6/D16 for frost alarm, external alarm, or fire damper exercise.

Configuration Codes and Factory Defaults

Overview of configuration codes for system setup and factory default values.

CORRIGO C10-LON Configuration Code Schematics

Configuration Code 1 (Functions A-L)

Detailed explanation of Configuration Code 1 for functions A through L.

Configuration Code 2 (Functions M-S)

Detailed explanation of Configuration Code 2 for functions M through S.