INSTRUCTION
i
Read this instruction before installation
and wiring of the product
TTC40F
Consult documentation in all cases where this symbol
is used, in order to nd out the nature of the potential
hazards and any actions to be taken
1
TTC40F
Triac controller for proportional control
of electric heating
TTC40F is a proportional controller for electric heating with automatic
voltage adaption. TTC40F pulses the whole load On - Off. The ratio
between On-time and Off-time is varied 0 - 100% to suit the prevailing
heat demand. The current is always switched at zero phase angle to
prevent RFI.
TTC40F can control both symmetrical Y-connected 3-phase heaters
and symmetrical or asymmetrical Delta-connected heaters.
TTC40F is only intended for electric heating control. The control prin-
ciple makes it unsuitable for motor- or lighting control.
TTC40F is intended for DIN-rail mounting.
Installation
Mount TTC40F on a DIN-rail in a cabinet or other enclosure.
Mount TTC40F vertically with the text right side up.
Protection class: IP20.
Ambient temperature: 0 - 40°C
N.B. TTC40F emits approx. 70W of heat at full output which must be
dissipated.
Wiring
Supply voltage
Terminals L1in, L2in and L3in.
Supply voltage: 210-255 or 380-415V AC
3 phase, 50 - 60 Hz with automatic voltage adaption.
Maximum current 40A/phase.
N.B. The supply voltage to TTC40F should be wired via an all-pole switch
with a minimum contact gap of 3mm.
N.B. TTC40F must be earthed.
1
1
1
3
2 3
4 5 6
7
8
9
L1
L2
L3
L3
L2
L1
Figure 1: Wiring of supply voltage and load
Load
Terminals L1out, L2out and L3out.
Resistive 3-phase heater without neutral
Maximum load: 5290W/phase at 230V phase - phase voltage (40A).
9200W/phase at 400V phase - phase voltage (40A).
Minimum load: 530W/phase at 230V phase - phase voltage (4A).
920W/phase at 400V phase - phase voltage (4A).
Main sensor and external set-point (gs 2-6)
Terminals 1and 4. Low voltage. Not polarity sensitive.
N.B. Terminals 2 and 3 are internally connected and are used to simplify
wiring when using external setpoint.
N.B. Choice of internal or external setpoint is done using switch 1.
1779F
MAR 14
EN
Figure 2: Wiring of room sensor TG-R530 or TG-R6xx when using
internal setpoint
1
2
TG-K3xx
TG-G1xx
3 4
12
3
2
TG-K3xx
TG-G1xx
TG-R4xx
3 4
12
2
1
TG-K3xx
TG-G1xx
TBI-xx
3
4
Figure 6: Wiring of external, separate sensor when using
potentiometer TBI-xx as external setpoint
Figure 3: Wiring of room sensor TG-R430 used as external
setpoint and sensor
Figure 4: Wiring of oor or duct sensor when using
internal setpoint
Figure 5: Wiring of external separate sensor when using TG-R4xx
as external setpoint
Question and Answer IconNeed help?

Do you have a question about the Regin TTC40F and is the answer not in the manual?

Regin TTC40F Specifications

General IconGeneral
Power consumption3.5 VA
Protection classIP20
Frequency50/60 Hz
Storage temperature-20...+70°C
Output voltage0-10 V DC

Summary

Installation

Wiring

Details on wiring supply voltage, load connections, and ensuring proper earthing for the TTC40F unit.

Load

Specifications for resistive 3-phase heaters including maximum and minimum load ratings for various voltages.

Main sensor and external set-point

Wiring instructions for main sensors and external set-points, including low voltage connections and switch settings.

Limiting sensor

Settings

Configuration of potentiometers (setpoint, min, max) and switches for internal/external setpoint and limiting functions.

Control principle

Explanation of TTC40F's proportional control, PID adaptation for different temperature changes, and RFI elimination.

External control signal

Start-up and fault finding

Steps for initial wiring checks, setpoint verification, and initial operational testing of the TTC40F unit.

Something wrong?

Diagnostic procedures for identifying issues with sensor resistance and the TTC40F's power output.

Related product manuals