Model B Series Rev. 03-14-2019 1 P/N 551-0202-02
MODEL B SERIES
SINGLE CHANNEL LOOP DETECTORS
INSTALLATION AND OPERATING INSTRUCTIONS
I. General
Please verify source voltage before applying power. The model designation indicates the input power required, output
configuration, sensitivity boost configuration, and Fail-Safe / Fail-Secure configuration for the detector as follows.
Model B-xx-xx-x Blank = Fail-Safe, S = Fail-Secure
Blank = Internal DIP switches set to True Presence
TM
/ Pulse-on-Entry
DP = Internal DIP switches set to True Presence
TM
/ True Presence
TM
SB = Internal DIP switch set to enable Sensitivity Boost
3 or 1 = 120 VAC
4 or 5 = 12 VDC / 24 VDC / 24 VAC
8 or 35 = 240 VAC
NOTE: Models B-3, B-4 and B-8 are fitted with a rear mounted, 11 pin, and Amphenol style connector. Models
B-1, B-5, and B-35 are fitted with a rear mounted, 10-pin, MS style connector.
The detector is factory configured for either Fail-Safe or Fail-Secure operation (see unit side label). The output state of
each output relay in either Fail-Safe or Fail-Secure mode is listed in the table below.
Relay
Fail-Safe
Fail-Secure
Power Failure
Loop Failure
Power Failure
Loop Failure
A
Call
Call
No Call
No Call
B
No Call
No Call
No Call
No Call
II. Indicators and Controls
i. Power / Detect / Fail LEDs
The detector has one green and two red LED indicators that are used to provide an indication of the detector’s
power status, output state, and/or loop failure conditions. The table below lists the various indications and their
meanings.
PWR (Power) LED
DET (Detect) LED
FAIL LED
No power or low power
Output(s) Off
Loop OK
Normal power to detector
Output(s) On
Open Loop
N/A
4 Hz (50% duty cycle)
Two second timing
delay activated
1 Hz (50% duty cycle)
Shorted Loop
1 Hz (5% duty cycle)
Waiting for release of FREQ push-
button to enter diagnostics mode
(See Failed Loop Diagnostics)
NOTE: If the supply voltage drops below 75% of the nominal level, the PWR LED will turn off, providing a
visual indication of low supply voltage. Model B detectors will operate with supply voltage as low as 70% of
nominal supply voltage.
ii. Frequency LEDs:
The four red LED indicators provide an indication of the current detector operating frequency.
iii. Front Panel Pushbutton Switches:
Two momentary contact pushbutton switches are used to control the following.
RESET - Push the front panel mounted pushbutton labeled RESET to reset the detector.

Other manuals for Reno A&E B Series

Question and Answer IconNeed help?

Do you have a question about the Reno A&E B Series and is the answer not in the manual?

Reno A&E B Series Specifications

General IconGeneral
BrandReno A&E
ModelB Series
CategorySecurity Sensors
LanguageEnglish

Summary

General Detector Information

Model Designation and Configuration

Explains model naming conventions for power, output, sensitivity, and fail-safe/secure settings.

Fail-Safe and Fail-Secure Output States

Details relay output states for power and loop failure conditions in Fail-Safe vs. Fail-Secure modes.

Detector Indicators and Controls

Power, Detect, and Fail LED Indicators

Describes the meaning and status of the Power, Detect, and Fail LEDs on the detector.

Frequency LEDs

Explains the four red LEDs indicating the detector's current operating frequency.

Front Panel Pushbutton Switches

Details the function of the RESET and FREQ pushbuttons on the detector's front panel.

Internal DIP Switch Settings

Internal DIP Switch Functions

Lists the functions and factory default settings for each of the eight internal DIP switches.

Sensitivity Settings (DIP Switches 1-3)

Explains how DIP switches 1, 2, and 3 are used to select one of eight sensitivity levels.

Output Delay Setting (DIP Switch 4)

Describes how DIP switch 4 enables a two-second delay for output relays after vehicle detection.

Sensitivity Boost (DIP Switch 5)

Explains how DIP switch 5 temporarily increases sensitivity to prevent dropouts with high-bed vehicles.

Relay B Pulse Mode (DIP Switch 6)

Details how DIP switch 6 configures Relay B for pulse output on entry or exit.

Presence Hold Time (DIP Switch 7)

Explains DIP switch 7 for selecting Limited Presence or True Presence™ hold times for Output A.

Relay B Output Mode (DIP Switch 8)

Describes DIP switch 8 for setting Relay B to Pulse or Presence mode.

Operational Features and Diagnostics

Call Memory Functionality

Explains how the detector remembers a call state after a brief power interruption.

Failed Loop Diagnostics

Describes how the FAIL LED indicates loop status and how to retrieve stored failure types.

Pin Connections and Wiring

Wiring Harness Pinouts

Details pin connections for Models B-3, B-4, B-8 (11-pin) and B-1, B-5, B-35 (10-pin) harnesses.

Warnings and Loop Installation

General Warnings

Provides recommendations for twisted pair wiring and soldered connections for reliable operation.

Loop Installation Guidelines

Explains how loop size, shape, and proximity to gates influence detection characteristics.

Loop Installation Saw Cut Method

Details the step-by-step process for cutting saw slots and installing loop wire for pavement.