9.2 Ignition Controller Lockout indicator Light Repeatedly Comes "ON"
no
yes
no yes
no no
yes
no
yes
yes
no
yes
no
yes
check
electronic
ignition
control
Place in normal
operation
check multi
functional
gas valve
Spark visible, still no
flame
Is there 220 to 240V
between terminals
13 & N
Check electronic
ignition control
correct the gas supply
pressure
During 5" trial for ignition
is a spark visible?
Check electronic
ignition control
Check spark gap and
ceramic & check
spark wire &
connector
Is a spark visible ?
Check flame signal. Is it
greater than 1,0 micro
Amps?
Check flame signal using
micro amp meter. Is signal
greater than 1,0 micro
Amps?
During 5" trial for ignition is
a flame visible in ths view
port?
Correct polarity
Does the inlet gas
pressure agree with the
data badge
Is polarity of mains
correct?
Remove corrosion
& scale from flame
sensing rod & clean
ceramic insulation
Wait 15" and press
reset button