Table 2 :Injector size and burner pressures
Model1220303545506075100120145
Injector quantity 5 5 6 8 10 8 8 10 12 10 12
mm 1,50 2,10 2,10 2,20 2,20 2,40 2,70 2,70 2,90 3,40 3,40
marking 150 210 210 220 220 240 270 270 290 340 340
Burner pressure (1) mbar 8,10 8,00 7,25 7,10 6,90 9,20 8,50 8,30 7,50 9,20 9,00
Inlet pressure mbar
Injector quantity - 5 6 8 10 8 8 10 12 10 12
mm - 1,15 1,15 1,15 1,15 1,40 1,45 1,45 1,50 1,95 1,90
marking - 115 115 115 115 140 145 145 150 195 190
Burner pressure (1) mbar - 35,80 35,80 36,20 35,90 30,10 35,60 35,40 34,40 30,70 30,60
Inlet pressure mbar
Model1220303545506075100120145
Injector quantity - 5 6 8 10 8 - 10 - - -
mm - 2,40 2,40 2,40 2,40 2,60 - 3,00 - - -
marking - 240 240 240 240 260 - 300 - - -
Burner pressure (1) mbar - 8,30 8,20 8,35 8,25 11,40 - 9,25 - - -
Inlet pressure mbar
Injector quantity - 5 6 8 10 8 - 10 - - -
mm - 2,60 2,60 2,50
2,60 3,40
-
3,90
---
marking - 260 260 250
260 340
-
390
---
Burner pressure (1) mbar - 8,25 8,45 9,55
8,40 6,00
-
5,25
---
Inlet pressure mbar
Model1220303545506075100120145
Injector quantity 5** 5 6 8 10 8 8 10 12 10 12
mm 1,50 2,10 2,10 2,20 2,20 2,40 2,70 2,70 2,90 3,40 3,40
marking 150 210 210 220 220 240 270 270 290 340 340
Burner pressure (1) mbar 8,10 8,00 7,25 7,10 6,90 9,20 8,50 8,30 7,50 9,20 9,00
Inlet pressure mbar
Injector quantity - 5 6 8 10 8 8 10 12 10 12
mm - 1,15 1,15 1,15 1,15 1,40 1,45 1,45 1,50 1,95 1,90
marking - 115 115 115 115 140 145 145 150 195 190
Burner pressure (1) mbar - 35,80 35,80 36,20 35,90 30,10 35,60 35,40 34,40 30,70 30,60
Inlet pressure mbar
(* ): Inlet pressure for Hungary = 25mbar
(**): no nat gas for Germany
Model1220303545506075100120145
Injector quantity 5 5 6 8 10 8 8 10 12 10 12
mm 1,50 2,10 2,10 2,20 2,20 2,40 2,70 2,70 2,90 3,40 3,40
marking 150 210 210 220 220 240 270 270 290 340 340
Burner pressure (1) mbar 8,10 8,00 7,25 7,10 6,90 9,20 8,50 8,30 7,50 9,20 9,00
Inlet pressure mbar
Injector quantity - 5 6 8 10 8 8 10 12 10 12
mm - 1,15 1,15 1,15 1,15 1,40 1,45 1,45 1,50 1,95 1,90
marking - 115 115 115 115 140 145 145 150 195 190
Burner pressure (1) mbar - 28,06 28,06 28,37 28,14 23,59 27,90 27,75 26,96 24,10 24,00
Inlet pressure mbar
Model1220303545506075100120145
Injector quantity 5 5 6 8 10 8 8 10 12 10 12
mm 1,50 2,10 2,10 2,20 2,20 2,40 2,70 2,70 2,90 3,40 3,40
marking 150 210 210 220 220 240 270 270 290 340 340
Burner pressure (1) mbar 8,10 8,00 7,25 7,10 6,90 9,20 8,50 8,30 7,50 9,20 9,00
Inlet pressure mbar
Injector quantity - 5 6 8 10 8 8 10 12 10 12
mm - 1,20 1,20 1,20 1,20 1,45 1,50 1,50 1,60 1,95 1,90
marking - 120 120 120 120 145 150 150 160 195 190
Burner pressure (1) mbar - 28,60 28,80 29,20 28,80 28,10 28,50 28,40 27,70 26,40 25,30
Inlet pressure mbar
(1) : with open service door
Prop. Gas
G31
Injector size
30
Romania
LCSA-4
Nat. Gas
G20
Injector size
20
G2,350
Injector size
13
Belarus, China, Croatia, Czech Republic, Cyprus, England, Estonia, Greece, Iceland, Latvia, Lithuania, Montenegro, New Zealand, Portugal, Serbia, Slovenia,
Slovakia, South Africa, Spain , Turkey, Poland
Nat. Gas
G20
Injector size
20
Prop. Gas
G31
Injector size
37
LCSA-4
LCSA-4
Special poland
G27
Injector size
20
Nat. Gas
G20
Injector size
20
Prop. Gas
G31
Injector size
30
LCSA-4
LCSA-4
Bulgaria, Denmark, Finland, Norway, Sweden
Austria, Germany, Hungary, Russian Federation, Ukraine
Nat. Gas
G20
Injector size
20(*)
Prop. Gas
G31
Injector size
50