F
IGURE 26
TWO FURNACE VENTING THROUGH ROOF
8"
MINIMUM 12" ABOVE AVERAGE
SNOW ACCUMULATION. MAXIMUM
O
F 24 IN. ABOVE ROOF.
8. Painted surfaces must be sound
and in good condition with no
cracking, peeling, etc. Painted
surfaces will require
maintenance.
9. Do not expose 3" x 2" reducer/
bushing to outdoor ambient
temperatures.
MULTIVENTING
IF VENTING TWO OR MORE
FURNACES NEAR EACH OTHER IS
REQUIRED, EACH FURNACE MUST
BE INDIVIDUALLY VENTED NO
COMMON VENTING IS PERMITTED.
See Figures 26 and 27 for positioning
of the terminations. When more than
two furnaces are to be vented, there
must be at least 4 feet between the
first two furnaces and the third, etc.
F
IGURE 27
TWO FURNACE VENTING THROUGH WALL
EXHAUST VENT
M
ODELS 06-07
TO BE REDUCED TO
1
-1/2” PVC LAST 12”.
3
MINIMUM
24” MAXIMUM
3
MINIMUM
24” MAXIMUM
8” MINIMUM
2
4” MAXIMUM
8” MINIMUM
24” MAXIMUM
TWO-PIPE VENTING
CONCENTRIC VENTING
S
EE CONCENTRIC
VENT SECTION
ON PAGE 23
FOR MORE
INFORMATION.
TWO-PIPE VENTING
CONCENTRIC VENTING
8"
MAXIMUM 1"
DISTANCE
FROM WALL
MINIMUM 12"
ABOVE GRADE
6' MINIMUM
10' RECOMMENDED
NOTE: Measurements apply to both
RXGY-E03 and RXGY-G01