General safety precautions and warnings for operating the water heater.
View current alarms, get more info, and access alarm history.
Provides guidance for specific alarms and troubleshooting steps.
Unit locks out after 27 failed ignition cycles; troubleshooting steps provided.
Flame rectification signal lost three times in one heating cycle; check gas pressure, vents, rod.
Intake pressure switch opens due to blockage in intake venting; check wiring and tubing.
Proof of Fan switch is open during heating; check wiring, tubing, and air intake.
Proof of Fan switch is open during pre-purge; check wiring, tubing, and blower operation.
Proof of Fan switch is open during post-purge; check wiring, tubing, and air intake.
Exhaust pressure switch opens due to excess pressure in exhaust venting.
Proof of Fan switch is closed when blower is off; check blower operation and switch continuity.
Tank temperature exceeded allowable temp; check probe, wiring, and ECO switch.
Combustion gases are too hot at exhaust tee; check wires, elbow, Molex, and sensor readings.
Control senses flue temperature sensor is open or disconnected. Refer to A017.
Control senses a short in the flue temperature sensor or wiring harness. Refer to A017.
Water temperature probe not connected or thermistor damaged; check Molex, wiring, and resistance.
Upper tank temperature exceeded 205°F; check probe, wiring, or ignition board.
Short detected in ECO/temperature probe or wiring. Refer to A022.
Control does not detect blower RPM; check blower voltage, wiring, or blower itself.
Blower RPM mismatch detected; check wiring harness and potentially replace blower.
Flame detected prior to ignition; check for flame, earth ground, or replace controller.
Flame signal detected after heating cycle closed; check flame, gas valve, or flame rod.
Unit fails ignition 9 times, gives A029. Refer to A001 for troubleshooting.
Unit lost flame signal during heating; attempts 3 times, then locks out with A002.
Water leak detected by control; check for leaks, sensor, or resolve leak.
No water detected; ensure tank is full, check for anode alerts, and follow diagnostic steps.
Gas pressure switch is open; check wiring, inlet gas pressure, or replace switch.
Lower tank temperature sensor is open; check harness, resistance, or replace sensor/board.
Short detected in lower temperature probe wiring; check probe, wiring, or board.
Unit fails ignition 9 times, gives A029. Refer to A001 for troubleshooting.