Dual 7-Segment
LEDs Display
Code
Diagnostic Description
Status/Possible Cause Troubleshooting
Information
29 High Pressure Control Open
T
he ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
L29 Active Protection High Pressure
Control Trip
LPC has opened 3 times in the same cooling
operation, the ICC has locked out the compressor
to protect it. ICC alternately flashes L and 29
FLASHING
L
80 Low Air Flow
The ICC detects that the indoor unit is
not providing the minimum airflow
requirements.
Misapplied/wrong indoor air mover
replace with properly sized unit.
83 Condenser Coil Temperature Fault
The sensor detects an abnormally low or
high coil temperature
Replace the sensor
Check sensor is installed correctly on control
84 Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or
high outdoor ambient temperature
Check unit placement If the outdoor unit is in
a high temperature area, wait until the ambient
temperature drops and check sensor reading.
Replace the sensor.
Check sensor is installed correctly on control
93 Internal Control Fault
The control is not functioning
properly.
Check control for proper system
operation.
Replace control
30 Fuse Open
The ICC detects the on-board fuse is open
The 3-amp fuse on the ICC is open.
Low voltage wiring at R and C is damaged or
miswired.
d1 No Shared Data Replace memory card with correct system
information.
d3 Airflow CFM Mismatch
The indoor air mover (air
handler/furnace) cannot supply the
required airflow for proper system
operation
Misapplied/wrong indoor air mover
replace with properly sized air
handler/furnace.
d4 (Device) Memory Card Invalid for
Device
The data in the memory card inserted
into the control board does not match
the data in the control.
Check memory card to ensure it matches
device
Check if memory card is present
d8 Old Shared Data
System data is obsolete
If system will not operate, order new
memory card to update system
information.