CONVENTIONAL THERMOSTAT WIRING
2) Resets the 3-minute anti-short cycle timer
3) Energizes the unit without a call for unit operation
If the 3-minute anti-short cycle timer or 30 second minimum run timer is active (a
flashing “c” or “C” is displayed on the dual 7-segment LEDs) and a call for unit
operation is present, TEST mode causes:
1) A “t” to display momentarily on the dual 7-segment display
Lower case “t”
2) The compressor will start
3) The display will change to a steady “c” or “C” to show the current call for unit
operation.
Note: If a call for unit operation is present at the end of TEST mode will cause the
unit to continue to operate.
If no call for unit operation is present, TEST mode causes
1) A steady “t” appears on the dual 7-segment LEDs
2) The compressor will start
3) The compressor will turn off after 5-seconds.
Note: Entering TEST mode without a call for unit operation will cause the com-
pressor to run 5-seconds.
Fault Recall Mode (TEST and SW2 Buttons)
Enter FAULT RECALL mode by pressing the TEST and SW2 buttons at the
same time with insulated probes for one (1) second and release.
When entering and exiting FAULT RECALL mode the top and bottom segments
of the dual 7-segment LEDs will illuminate.
Fault Recall Mode the top and bottom segments on the
right-hand are illuminated
When entering FAULT RECALL mode, the ICC will automatically scroll through
stored faults on the dual 7-segment LEDs.
Each fault is displayed one time with the top right-hand segment of the dual 7-
segment display activated between faults.
Each fault is displayed with the most recent fault displayed first.
A maximum of six individual faults can be stored
A maximum of three consecutive identical faults are stored.
A “0” will be displayed with no faults are stored
The ICC will automatically exit the FAULT RECALL mode after displaying stored
faults
IMPORTANT: The ICC stores the previous two weeks of history faults. The com-
plete stored fault history cannot be displayed using a conventional thermostat.
Clear Fault History (TEST and SW2 Buttons)
Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) sec-
onds with insulated probes and release.
The top and bottom segments of the dual 7-segment LEDs flash to indicate the
history has been cleared.
Fault history is cleared with the top and bottom LED
segments flash