FIGURE 1
DIMENSIONS AND INSTALLATION CLEARANCES
UNIT MODEL NUMBER EXPLANATION
(-)ARL – 036 JEC
E
C = EQUIPPED WITH THE
C
OMFORT CONTROL
2
S
YSTEM™
J-208/230-1-60
(NOMINAL CAPACITY)
0
24 = 24000 BTU/HR
0
36 = 36000 BTU/HR
0
48 = 48000 BTU/HR
0
60 = 60000 BTU/HR
L = DESIGN SERIES (R-410A)
R = 16 SEER
A
= REMOTE CONDENSING UNIT
TRADE NAME
BASE PAN
ALLOW 24" [610 mm]
ACCESS CLEARANCE
ALTERNATE LINE VOLTAGE
ENTRY (KNOCKOUT)
1
1
1
⁄32" [34 MM]
CONNECT THE LINE
VOLTAGE CONDUIT TO
THE BOTTOM OF THE
CONTROL BOX
AIR INLETS
(LOUVERS)
ALLOW 6” [152 mm]
MIN. CLEARANCE
3
SIDES
ACCESS
PANEL
AIR DISCHARGE
ALLOW 60" [1524 mm] CLEARANCE
TABLE 1
(-)ARL-JEC ELECTRICAL DATA
Model
Number
Phase
Frequency
(Hz)
Voltage
(Volts)
Compressor
Fan
Motor
(FLA)
Min. Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Outdoor Coil Weight
Min.
Amperes
Max.
Amperes
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s}
R-410a
Oz. [g]
Net
Lbs. [kg]
Shipping
Lbs. [kg]
Height
“H”
(Inches)
Length
“L”
(Inches)
Width
“W”
(Inches)
ELECTRICAL PHYSICAL DIMENSIONAL DATA
(RLA) (LRA)
(-)ARL-024JEC 1-60-208/230 10.3/10.3 52 0.8 14/14 20/20 20/20 15.8 [1.47] 1 2285 [1078] 117 [3311] 190 [86.2] 200 [90.7] 23 44-3/8 31-1/2
(-)ARL-036JEC 1-60-208/230 16.7/16.7 82 1.0 22/22 30/30 35/35 15.8 [1.47] 1 3900 [1841] 157 [4445] 236 [107] 246 [111.6] 33 44-3/8 31-1/2
(-)ARL-048JEC 1-60-208/230 21.2/21.2 96 1.0 28/28 35/35 45/45 15.8 [1.47] 1 3900 [1841] 154 [4354] 236 [107] 246 [111.6] 33 44-3/8 31-1/2
HS* 3500 [1652]
224 [6250] 305 [138.4] 315 [142.8] 33 44-3/8 31-1/2
(-)ARL-060JEC 1-60-208/230 25.6/25.6 118 2.8 35/35 45/45 60/60 23.0 [2.14] 2
LS* 2800 [1322]
*HS = high speed
*LS = low speed
BOTTOM VIEW SHOWING DRAIN OPENINGS
(\\\\\ SHADED AREAS).
LINE VOLTAGE
ENTRY
1
11
⁄32" [34 MM]
CONNECT THE LINE
VOLTAGE CONDUIT TO
THE BOTTOM OF THE
CONTROL BOX
LINE VOLTAGE
ENTRY
7
⁄8" [22 MM]
2.3 DIMENSIONS
2.4 ELECTRICAL & PHYSICAL DATA
6