EasyManua.ls Logo

Rheem RASL-JEC - Page 14

Rheem RASL-JEC
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
T
ABLE 5
(
-)ASL SUCTION LINE SIZING
SUCTION LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL
R-410A
System
Capacity
Model
Line Size
Connection
Size (Inch
I.D.) [mm]
Line Size
(Inch O.D.)
[mm]
Outdoor Unit ABOVE Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Total Equivalent Length - Feet [m]
5/8” [15.88] Same as Liquid Line Size Table
-024 3/4” [19.05] 3/4” [19.05]* NA
7/8” [22.23] NA
5/8” [15.88] Same as Liquid Line Size Table
-036 & -039 3/4” [19.05] 3/4” [19.05]* NA
7/8” [22.23] NA
5/8” [15.88] Same as Liquid Line Size Table
-048 7/8” [22.22] 3/4” [19.05] Same as Liquid Line Size Table
7/8” [22.23]* NA
3/4” [19.05] Same as Liquid Line Size Table
-060 7/8” [22.22] 7/8” [22.23]* NA
1-1/8” [28.58] NA
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.1] 150 [45.72]
Suction Line Size
S
UCTION LINE SIZE - OUTDOOR UNIT BELOW INDOOR COIL
R-410A
System
Capacity
Model
Line Size
Connection
Size
(Inch I.D.)
[mm]
Line Size
(Inch O.D.)
[mm]
Outdoor Unit BELOW Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Total Equivalent Length - Feet [m]
5/8” [15.88] Same as Liquid Line Size Table
-024 3/4” [19.05] 3/4” [19.05]* Same as Liquid Line Size Table NA
7/8” [22.23] NA
5/8” [15.88] Same as Liquid Line Size Table
-036 & -039 3/4” [19.05] 3/4” [19.05]* Same as Liquid Line Size Table
7/8” [22.23] NA
5/8” [15.88] Same as Liquid Line Size Table
-048 7/8” [22.22] 3/4” [19.05] Same as Liquid Line Size Table
7/8” [22.23]* Same as Liquid Line Size Table NA
3/4” [19.05] Same as Liquid Line Size Table
-060 7/8” [22.22] 7/8” [22.23]* Same as Liquid Line Size Table
1-1/8” [28.58] NA
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.1] 150 [45.72]
Suction Line Size
NOTES: Using suction line larger than shown in chart will result in poor oil return.
N/A = Application Not Recommended
*Standard Line Size
NOTES: Using suction line larger than shown in chart will result in poor oil return.
N/A = Application Not Recommended
*Standard Line Size

Related product manuals