26
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
Status/Possible Cause – Troubleshooting
Information
06 – Compressor Open Start Circuit
The ICC detects current in the Run
circuit but not in the Start circuit of the
compressor four (4) times in one
compressor call
• Check for damaged, miswired, or wrong
run capacitor
• Check for broken wires, loose connectors,
or miswired compressor
• Check compressor windings for continuity
6
c
ontinuing to operate and flash a “L” on the 7-segment LEDs followed by a “21”. Once
the outdoor ambient rises above 5°F the ICC will clear active protection automatically.
I
MPORTANT: This mode of active protection will automatically deactivate once the
o
utdoor temperature rises above 5°F. Wait until the outdoor ambient temperature rises
above 5°F before performing further diagnostics.
2) High Pressure Control Lockout
• I
f the HPC opens three (3) times during the same command for unit operation, the ICC
will lockout the compressor to keep it from continuing to operate and flash a L” on the 7-
segment LEDs followed by a “29”.
Active Protection – Code L29 – Open high pressure control
I
MPORTANT: This mode of active protection must be manually deactivated.
3) Locked Rotor
• T
he ICC will display a flashing “L” followed by a flashing “4” when a locked rotor
condition occurs.
Active Protection – Code L4 – Locked rotor
If the ICC detects the compressor has run less than 15 seconds for four (4) consecutive
starts during the same command for unit operation, the ICC will lockout the compressor
to keep it from continuing to operate and flash a “L” on the 7-segment LEDs followed by
a “4”.
IMPORTANT: This mode of active protection must be manually deactivated.
4) Open Start Circuit Lockout
05 – Open circuit (Compressor will not
Run)
• The ICC has received a command for
unit operation but no current is present in
the start and run circuits
• The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
• The ICC has had a protector trip for longer
than 4 hours.
• Check for damaged, miswired, or wrong run
c
apacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
11
d1 – No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch
T
he indoor air mover (air handler/furnace)
cannot supply the required airflow for
proper system operation
•
Misapplied/wrong indoor air mover – replace
w
ith properly sized air handler/furnace.
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
•
Motor protector open
•
Line voltage disconnected
0
1 – Long Run Time (Compressor)
The compressor has continuously run for
m
ore than 18 hours in the cooling mode.
• Low refrigerant charge
•
Air ducts have substantial leakage
• Dirty indoor air filter
• Dirty outdoor coil
02 – High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
• 21
• L21
• 29
• L29
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
•
Check thermostat wire connections (R, C, 1, &
2
)
•
Check thermostat location in zone (too close to
d
ischarge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
p
rotector trips have occurred and the
average run time for each trip is less than 15
seconds
• Bad run capacitor
• Low line voltage
• Excessive refrigerant in compressor
• Seized bearings in compressor
05 – Open Circuit (Compressor will not
Run)
• The ICC has received a command for
unit operation but no current is present in
t
he start and run circuits.
• The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
•
Check for damaged, miswired, or wrong run
capacitor
•
Check for broken wires, loose connectors, or
miswired compressor
•
Check compressor windings for continuity
• Check for open compressor internal protector
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
• Control transformer overloaded
• Low line voltage
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
11
d
1 – No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d
3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
proper system operation
• Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P
– Protector Trip
A command for compressor operation is
p
resent but no current is measured to the
compressor
•
Motor protector open
•
Line voltage disconnected
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
• Low refrigerant charge
• Air ducts have substantial leakage
• Dirty indoor air filter
•
Dirty outdoor coil
02 – High Pressure Control Open
T
he ICC detects the HPC is open.
Reference ICC codes:
• 21
• L21
• 29
•
L29
03 – Short Cycling
T
he ICC detects the run time for the past
f
our (4) compressor cycles is less than three
(3) minutes each.
• Check thermostat wire connections (R, C, 1, &
2
)
• Check thermostat location in zone (too close to
d
ischarge grill)
L4 – Locked Rotor
T
he ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
• Bad run capacitor
• Low line voltage
• Excessive refrigerant in compressor
•
Seized bearings in compressor
05 – Open Circuit (Compressor will not
Run)
• The ICC has received a command for
u
nit operation but no current is present in
the start and run circuits.
• The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
• Control transformer overloaded
• Low line voltage
11
d1 – No Shared Data
E
LECTRONICS GROUP TO
D
ESCRIBE
d3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
p
roper system operation
• Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P
– Protector Trip
A
command for compressor operation is
present but no current is measured to the
c
ompressor
• Motor protector open
• Line voltage disconnected
01 – Long Run Time (Compressor)
T
he compressor has continuously run for
m
ore than 18 hours in the cooling mode.
•
Low refrigerant charge
•
Air ducts have substantial leakage
• Dirty indoor air filter
•
Dirty outdoor coil
02 – High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
•
21
•
L21
•
29
• L29
0
3 – Short Cycling
The ICC detects the run time for the past
f
our (4) compressor cycles is less than three
(3) minutes each.
• Check thermostat wire connections (R, C, 1, &
2)
• Check thermostat location in zone (too close to
discharge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
a
verage run time for each trip is less than 15
seconds
•
Bad run capacitor
• Low line voltage
•
Excessive refrigerant in compressor
• Seized bearings in compressor
05 – Open Circuit (Compressor will not
Run)
• The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
• The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
• Control transformer overloaded
• Low line voltage
07 – Compressor Open Run Circuit
The ICC detects current in the Start
circuit but not in the Run circuit of the
compressor four (4) times in one
compressor call
• Check for damaged, miswired, or wrong
run capacitor
• Check for broken wires, loose connectors,
or miswired compressor
• Check compressor windings for continuity
6
continuing to operate and flash a “L” on the 7-segment LEDs followed by a “21”. Once
t
he outdoor ambient rises above 5°F the ICC will clear active protection automatically.
IMPORTANT: This mode of active protection will automatically deactivate once the
o
utdoor temperature rises above 5°F. Wait until the outdoor ambient temperature rises
a
bove 5°F before performing further diagnostics.
2) H
igh Pressure Control Lockout
• If the HPC opens three (3) times during the same command for unit operation, the ICC
w
ill lockout the compressor to keep it from continuing to operate and flash a L” on the 7-
segment LEDs followed by a “29”.
Active Protection – Code L29 – Open high pressure control
IMPORTANT: This mode of active protection must be manually deactivated.
3) Locked Rotor
• The ICC will display a flashing “L” followed by a flashing “4” when a locked rotor
condition occurs.
Active Protection – Code L4 – Locked rotor
If the ICC detects the compressor has run less than 15 seconds for four (4) consecutive
starts during the same command for unit operation, the ICC will lockout the compressor
to keep it from continuing to operate and flash a “L” on the 7-segment LEDs followed by
a “4”.
IMPORTANT: This mode of active protection must be manually deactivated.
4) Open Start Circuit Lockout
11
d1 – No Shared Data
E
LECTRONICS GROUP TO
D
ESCRIBE
d3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
p
roper system operation
• Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P
– Protector Trip
A
command for compressor operation is
present but no current is measured to the
c
ompressor
• Motor protector open
• Line voltage disconnected
01 – Long Run Time (Compressor)
T
he compressor has continuously run for
more than 18 hours in the cooling mode.
•
Low refrigerant charge
• Air ducts have substantial leakage
• Dirty indoor air filter
•
Dirty outdoor coil
02 – High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
•
21
• L21
•
29
• L29
03 – Short Cycling
The ICC detects the run time for the past
f
our (4) compressor cycles is less than three
(3) minutes each.
• Check thermostat wire connections (R, C, 1, &
2)
• Check thermostat location in zone (too close to
discharge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
• Bad run capacitor
• Low line voltage
• Excessive refrigerant in compressor
• Seized bearings in compressor
05 – Open Circuit (Compressor will not
Run)
• The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
• The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
• Control transformer overloaded
• Low line voltage
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
11
d1 – No Shared Data
E
LECTRONICS GROUP TO
D
ESCRIBE
d3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
p
roper system operation
• Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P
– Protector Trip
A command for compressor operation is
p
resent but no current is measured to the
compressor
•
Motor protector open
• Line voltage disconnected
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
•
Low refrigerant charge
•
Air ducts have substantial leakage
• Dirty indoor air filter
•
Dirty outdoor coil
02 – High Pressure Control Open
T
he ICC detects the HPC is open.
Reference ICC codes:
•
21
•
L21
• 29
•
L29
0
3 – Short Cycling
The ICC detects the run time for the past
f
our (4) compressor cycles is less than three
(3) minutes each.
• Check thermostat wire connections (R, C, 1, &
2
)
• Check thermostat location in zone (too close to
d
ischarge grill)
L4 – Locked Rotor
T
he ICC detects four (4) consecutive
protector trips have occurred and the
a
verage run time for each trip is less than 15
seconds
• Bad run capacitor
• Low line voltage
•
Excessive refrigerant in compressor
• Seized bearings in compressor
05 – Open Circuit (Compressor will not
Run)
• The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
• The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
• Control transformer overloaded
• Low line voltage
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
• Control transformer overloaded
• Low line voltage
11
d1 – No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch
T
he indoor air mover (air handler/furnace)
c
annot supply the required airflow for
proper system operation
• Misapplied/wrong indoor air mover – replace
w
ith properly sized air handler/furnace.
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
• Motor protector open
•
Line voltage disconnected
0
1 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
• Low refrigerant charge
• Air ducts have substantial leakage
• Dirty indoor air filter
• Dirty outdoor coil
02 – High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
• 21
• L21
• 29
• L29
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
•
Check thermostat wire connections (R, C, 1, &
2)
•
Check thermostat location in zone (too close to
discharge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
• Bad run capacitor
• Low line voltage
• Excessive refrigerant in compressor
• Seized bearings in compressor
05 – Open Circuit (Compressor will not
Run)
• The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
• The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
• Control transformer overloaded
• Low line voltage
21 – Low Pressure Control Open
The ICC detects the LPC is open.
Note: The low pressure control is ignored
for the first 90 seconds of compressor
operation
• Unit has low refrigerant charge
• Indoor coil is frozen (cooling mode)
• Dirty indoor coil or filter (cooling mode)
• Indoor blower is not running (cooling mode)
• Outdoor coil is frozen (heating mode)
• Expansion valve is not operating correctly
12
21 – Low Pressure Control Open
The ICC detects the LPC is open.
Note: The low pressure control is ignored
for the first 90 seconds of compressor
operation
• Unit has low refrigerant charge
• Indoor coil is frozen (cooling mode)
• Dirty indoor coil or filter (cooling mode)
• Indoor blower is not running (cooling mode)
• Outdoor coil is frozen (heating mode)
• Outdoor fan is not running (heating mode)
• Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to
three (3) consecutive LPC trips on the same
command for unit operation
27 – Low Line Voltage or No Line Voltage
Fault
• Check incoming line voltage to the disconnect
and unit
• Check wiring connections
28 – High Line Voltage Fault
• Check line voltage
29 – High Pressure Control Open
The ICC detects the HPC is open
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure
Control Trip
The ICC has locked out the compressor due to
three (3) consecutive HPC trips on the same
command for unit operation
30 – Fuse Open
The ICC detects the on-board fuse is open
• The 3-amp fuse on the ICC is open.
• Low voltage wiring at R and C is damaged or
miswired.
83 – Condenser Coil Temperature Fault
The sensor detects an abnormally low or
high coil temperature
• Replace the sensor
84 – Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or
high outdoor ambient temperature
• Check unit placement – If the outdoor unit is in
a high temperature area, wait until the ambient
temperature drops and check sensor reading.
• Replace the sensor.
90 – Communication Fault
The ICC detects and internal fault condition
• Replace the ICC.
L21 – Active Protection Low Pressure
Control Trip
LPC has opened 3 times in the same cooling
operation, the ICC has locked out the compressor
to protect it. ICC alternately flashes L and 21
12
21 – Low Pressure Control Open
The ICC detects the LPC is open.
Note: The low pressure control is ignored
for the first 90 seconds of compressor
operation
• Unit has low refrigerant charge
• Indoor coil is frozen (cooling mode)
• Dirty indoor coil or filter (cooling mode)
• Indoor blower is not running (cooling mode)
• Outdoor coil is frozen (heating mode)
• Outdoor fan is not running (heating mode)
• Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to
three (3) consecutive LPC trips on the same
command for unit operation
27 – Low Line Voltage or No Line Voltage
Fault
• Check incoming line voltage to the disconnect
and unit
• Check wiring connections
28 – High Line Voltage Fault
• Check line voltage
29 – High Pressure Control Open
The ICC detects the HPC is open
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure
Control Trip
The ICC has locked out the compressor due to
three (3) consecutive HPC trips on the same
command for unit operation
30 – Fuse Open
The ICC detects the on-board fuse is open
• The 3-amp fuse on the ICC is open.
• Low voltage wiring at R and C is damaged or
miswired.
83 – Condenser Coil Temperature Fault
The sensor detects an abnormally low or
high coil temperature
• Replace the sensor
84 – Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or
high outdoor ambient temperature
• Check unit placement – If the outdoor unit is in
a high temperature area, wait until the ambient
temperature drops and check sensor reading.
• Replace the sensor.
90 – Communication Fault
The ICC detects and internal fault condition
• Replace the ICC.
27 – Low Line Voltage or No Line Voltage
Fault
• Check incoming line voltage to the disconnect
and unit
• Check wiring connections
12
21 – Low Pressure Control Open
The ICC detects the LPC is open.
Note: The low pressure control is ignored
for the first 90 seconds of compressor
operation
• Unit has low refrigerant charge
• Indoor coil is frozen (cooling mode)
• Dirty indoor coil or filter (cooling mode)
• Indoor blower is not running (cooling mode)
• Outdoor coil is frozen (heating mode)
• Outdoor fan is not running (heating mode)
• Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to
three (3) consecutive LPC trips on the same
command for unit operation
27 – Low Line Voltage or No Line Voltage
Fault
• Check incoming line voltage to the disconnect
and unit
• Check wiring connections
28 – High Line Voltage Fault
• Check line voltage
29 – High Pressure Control Open
The ICC detects the HPC is open
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure
Control Trip
The ICC has locked out the compressor due to
three (3) consecutive HPC trips on the same
command for unit operation
30 – Fuse Open
The ICC detects the on-board fuse is open
• The 3-amp fuse on the ICC is open.
• Low voltage wiring at R and C is damaged or
miswired.
83 – Condenser Coil Temperature Fault
The sensor detects an abnormally low or
high coil temperature
• Replace the sensor
84 – Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or
high outdoor ambient temperature
• Check unit placement – If the outdoor unit is in
a high temperature area, wait until the ambient
temperature drops and check sensor reading.
• Replace the sensor.
90 – Communication Fault
The ICC detects and internal fault condition
• Replace the ICC.
28 – High Line Voltage Fault • Check line voltage
12
21 – Low Pressure Control Open
The ICC detects the LPC is open.
Note: The low pressure control is ignored
for the first 90 seconds of compressor
operation
• Unit has low refrigerant charge
• Indoor coil is frozen (cooling mode)
• Dirty indoor coil or filter (cooling mode)
• Indoor blower is not running (cooling mode)
• Outdoor coil is frozen (heating mode)
• Outdoor fan is not running (heating mode)
• Expansion valve is not operating correctly
FLASHING
L21 – Active Protection
Low Pressure
Control Trip
The ICC has locked out the compressor due to
three (3) consecutive LPC trips on the same
command for unit operation
27 – Low Line Voltage or No Line Voltage
Fault
• Check incoming line voltage to the disconnect
and unit
• Check wiring connections
28 – High Line Voltage Fault
• Check line voltage
29 – High Pressure Control Open
The ICC detects the HPC is open
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
FLASHING
L29 – Active Protection High Pressure
Control Trip
The ICC has locked out the compressor due to
three (3) consecutive HPC trips on the same
command for unit operation
30 – Fuse Open
The ICC detects the on-board fuse is open
• The 3-amp fuse on the ICC is open.
• Low voltage wiring at R and C is damaged or
miswired.
83 – Condenser Coil Temperature Fault
The sensor detects an abnormally low or
high coil temperature
• Replace the sensor
84 – Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or
high outdoor ambient temperature
• Check unit placement – If the outdoor unit is in
a high temperature area, wait until the ambient
temperature drops and check sensor reading.
• Replace the sensor.
90 – Communication Fault
The ICC detects and internal fault condition
• Replace the ICC.