EasyManuals Logo
Home>Rheem>Furnace>RGTK-12ERAJS Series

Rheem RGTK-12ERAJS Series User Manual

Rheem RGTK-12ERAJS Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
25
FIGURE 17
ALTERNATE HORIZONTAL DIRECT VENT TERMINATION
SEE DETAIL A
24 MAX.
PIPE
SUPPORT
STRAP
3 MAX.
NOTE: 3-1/2
MAX. WHEN
D04 KIT IS
USED.
EXHAUST VENT
2
1
/2" PVC FOR MODELS WITH 120,000 BTU INPUT
(KIT NO. (-)XGY-D04)
2" PVC FOR MODELS WITH INPUTS OF 90,000 AND
120,000 BTU. REDUCE TO 1
1
/2" FOR MODELS WITH
INPUTS OF 45,000 THRU 75,000 BTU (SEE DETAIL A).
ELBOWS AND RISERS ARE 2" PVC.
INTAKE VENT
2
1
/2" PVC FOR MODELS WITH
120,000 BTU INPUT.
2" PVC ELBOWS AND RISER
MODELS WITH INPUTS OF 45,000
THRU 105,000 BTU.
USE KIT NO. (-)XGY-D02/D02A WHEN 2"
PIPE IS USED BETWEEN FURNACE AND
OUTSIDE WALL. USE KIT NO. (-)XGY-
D03/D03A WHEN 3" PIPE IS USED.
I339
Insulate the entire length of vent
pipe, between the elbow where the
pipe exits the wall and the elbow
where the termination is made, with
a closed-cell insulation, such as
“Arm-a-Flex” or “Rub-a-Tex” with a
minimum of 1/2” thickness.
All elbows installed on the exterior
of the building must be of the long
sweep nature.
As required for the horizontal piping
ran within the structure, any pipe
ran horizontal outside the structure
must slope upward a minimum of
1/4” per foot run so that condensate
drains toward the furnace.
From the top elbow in the exhaust
pipe, extend a length of PVC pipe
outward so that it terminates exactly
12 inches from the wall. See Figure
17. Reduce the exhaust pipe
extension to is 1
1
2 inch pipe for
45,000 BTUH through 75,000 BTUH
units.
The 45,000 BTUH unit only uses kit
(-)XGY-D02/D02A. The 60,000 BTUH
and 75,000 BTUH downflow only
units may use kits (-)XGY-D02/D02A
or (-)XGY-D03/D03A depending on
pipe lengths and number of elbows.
Use kit (-)XGY-D03/D03A with 90,000
BTUH downflow through 120,000
BTUH units or
upflow 90,000 or
120,000. The (-)XGY-D04/D04A kit
only applies to the 120,000 BTUH
unit using an alternate termination
and excessively long runs. See
Table 4.
The following are parts lists for the
(-)XGY-D02/D02A, (-)XGY-D03/D03A
and (-)XGY-D04/D04A alternate
horizontal direct vent termination kits:
(-)XGY-D02/D02A
1. 2-in. tee with reducer assembly
2.
1
2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. 1
1
2-in. PVC nipple with coupling
6. PVC strap
7. vent template
(-)XGY-D03/D03A
1. 3-in. tee with reducer assembly
2.
1
2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. PVC strap
6. vent template
(-)XGY-D04/D04A
1. 2
1
2-in. PVC elbow
2. 3" x 2
1
2" PVC bushing
3. 2
1
2" x 6
1
2" long PVC pipe
4. 2
1
2" x 16" long PVC pipe
5. 2
1
2" x 21" long PVC pipe
6. PVC vane
7.
3-in. tee with reducer assembly
8. 6-in. dia.
1
2-in. PVC trap
9. PVC strap
10. vent template
NOTE: The (-)XGY-D04/D04A kit only
applies to the 120,000 BTUH unit
using an alternate termination and
excessively long runs.
3
4
EXHAUST
VANE
INTAKE
OPTIONAL
INTAKE
DETAIL B
EXHAUST / INTAKE RELATIONSHIP
DETAIL A
EXHAUST VENT FOR
MODELS WITH
INPUT OF 45,000 THRU
75,000 BTU
DETAIL C
COMBUSTION AIR
TERMINATION
4" FROM
WALL
12"
FROM
WALL
1-1/2"
PIPE
12" FROM
WALL
(-)XGY-D02A
1. 2” Tee assembly w/
1
2 drain
connection
2.
1
2 PVC-5” diameter trap
3. Wind deflector vane
4. Vent template
(-)XGY-D03A
1. 3” Tee assembly w/
1
2 drain
connection
2.
1
2 PVC-5” diameter trap
3. Wind deflector vane
4. Vent Template
(-)XGY-D04A
1. 3” Tee assembly w/
1
2 drain
connection
2.
1
2 PVC-6” diameter trap
3. Wind deflector vane
4. Vent template

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem RGTK-12ERAJS Series and is the answer not in the manual?

Rheem RGTK-12ERAJS Series Specifications

General IconGeneral
BrandRheem
ModelRGTK-12ERAJS Series
CategoryFurnace
LanguageEnglish

Related product manuals